Appendix
Ecograph T, RSG35
152
Hauser
Description
Switches the appropriate output in the limit value state.
Options
Not used, Relay x
Factory setting
Not used
LV messages
Navigation
Expert → Application → Limits → Limit x → LV messages
Direct access code: 450007-0xx
Examples: Set point 1: 450007-000; Set point 30: 450007-029
Description
"Do not acknowledge": Alarm condition is signaled by highlighting the tag name in red (no
message is output).
"Acknowledge": In the event of an alarm, a message is also displayed. This message then
has to be acknowledged.
Options
Do not acknowledge, Acknowledge
Factory setting
Do not acknowledge
Save event
Navigation
Expert → Application → Limits → Limit x → Save event
Direct access code: 450008-0xx
Examples: Set point 1: 450008-000; Set point 30: 450008-029
Description
Stores a message in the event log on limit value violation.
Options
No, Yes
Factory setting
Yes
Event text LV on
Navigation
Expert → Application → Limits → Limit x → Event text LV on
Direct access code: 450009-0xx
Examples: Set point 1: 450009-000; Set point 30: 450009-029
Description
This text (including date and time) is shown on the display and/or stored in the event log.
Only available if "LV messages" is set to "Acknowledge" or "Save message" is set to "Yes".
If no text is entered, the device generates its own text (e.g. Analog 1 > 100%).
User entry
Text (max. 22 characters)