Ecograph T, RSG35
Electrical connection
Hauser
19
Further units
Termination
resistor
(typical 120 )
Ω
To PC: Cable with
9 pol. Sub-D plug
RxD - 3 GND - 5
TxD - 2
To PC: Cable with
25 pol. Sub-D
plug
To modem: Cable with
9 pol. Sub-D socket
To modem: Cable with
25 pol. Sub-D socket
A0019305-EN
Type
Pin of the SUB-D9 socket
1 2
3
4 5
6 7 8
9
RS232
assignment
TxD (data
output)
RxD (data
input)
GND
RS485
assignment
GND
RxD/TxD –
RxD/TxD +
Unoccupied connections should be left empty.
Maximum cable length:
RS232: 2 m (6.6 ft)
RS485: 1000 m (3280 ft)
Only one interface can be used at any one time (RS232 or RS485).
6.3.9
Ethernet connection (rear of device)
The Ethernet interface can be used to integrate the device via a hub or switch into a PC
network (TCP/ IP Ethernet). A standard patch cable (e.g. CAT5E) can be used for the
connection. Using DHCP, the device can be fully integrated into an existing network
without the need for additional configuration. The device can be accessed from every PC in
the network.
• Standard: 10/100 Base T/TX (IEEE 802.3)
• Socket: RJ-45
• Max. cable length: 100 m
• Galvanic isolation; testing voltage: 500 V