Operation
Fieldgate FXA42
104
Hauser
The COM server has been successfully initialized.
Diagram loaded
A diagram has been successfully loaded.
Web configuration modules initialized
The web configuration modules, which accept the configuration data from the Settings
page, have been successfully initialized.
Update exporter module initialized
The update exporter module, which exports the configuration to an update package, has
been successfully initialized.
Update web service initialized
The update web service, which manages the upload of update packages via the local web
server, has been successfully initialized.
Running
The run-time system has finished initialization.
Starting update from external medium.
The user has triggered an update from the external medium.
Link detected at Ethernet (<interface index>).
The Ethernet interface with the index indicated has been connected to the network.
Restarting DHCP configuration at Ethernet (<interface index>).
The run time system is trying to get a new IP configuration for the Ethernet interface with
the index indicated from a DHCP server.
DHCP configuration completed at Ethernet (<interface index>).
The run time system has received a new IP configuration for the Ethernet interface with
the index indicated from a DHCP server.
Power fail handling not supported
The device is not equipped with a power fail circuit. Data (e.g. portal variables) cannot be
stored retentively.
Not enough power fail capacity
The device is equipped with a power fail circuit, but the capacity supplied is not sufficient
to store data (e.g. portal variables) retentively.
Retentive data could not be loaded.
Retained data (e.g. portal variables) could not be loaded although the device is equipped
with a power fail circuit. This message appears when the device is started for the very first
time. If it occurs later, there is probably a problem with the power fail circuit.
The internal flash drive seems to be weak.
A write operation to the internal flash drive needed to be retried several times. This is an
indication that the flash drive is reaching the end of its life.
Flash write error. The internal flash drive is probably defect.
A write operation to the internal flash drive failed. The flash drive seems to have reached
the end of its life. The device is no longer usable.
One or more certificates could not be loaded.
At least one of the SSL certificate files could not be loaded.
Could not initialize NAT/firewall service. (<error code>)
The NAT and firewall service could not be initialized. The message also shows an internal
error code returned by the service's initialization routine.