Fieldgate FXA42
Operation
Hauser
81
Settings
Description
Unit
The input's measurement unit.
Minimum input range The input's minimum current value, measured in milliampere.
Maximum input
range
The input's maximum current value, measured in milliampere.
Scaling
The scaling may be calculated either by using a Min/Max value pair, or by providing a
linearization table.
Minimum scale
Minimum scaled value. This field is enabled when the
Range
option is selected in the
Scaling field.
Maximum scale
Maximum scaled value. This field is enabled when the
Range
option is selected in the
Scaling field.
Display scaled values
on home page
This check box defines whether the values on the home page and in the editor are to be
displayed in milliampere or in the scaled unit.
Limit High
The input's
High High
limit, measured in the scaled unit.
Limit High
The input's
High
limit, measured in the scaled unit.
Limit Low
The input's
Low
limit, measured in the scaled unit.
Limit Low Low
The input's
Low Low
limit, measured in the scaled unit.
Hysteresis
This value defines an offset value below the
High
and
High High
limits and above the
Low
and
Low Low
limits. The configured offset delays the resetting of an alarm. The
value is measured in the scaled unit.
Gradient limit
The input's gradient limit, measured in the scaled unit. This limit value triggers an
alarm if the input's value is above this limit for a certain time.
Time period
The time after which a Gradient Limit Alarm should be triggered.
8.4.9
Digital inputs
The digital inputs of the Fieldgate FXA42 can be configured on this page. On the left side
of the page the user may select one of the 4 different inputs by clicking the corresponding
tab. The settings for each of the 4 inputs are identical.
Clone settings
In order to make the configuration easier, the user may copy the current settings of one
input to another one. To do this, the user should first select the input from which the
settings are to be copied. Once you click the
Clone
button, all the settings from the
selected source input are copied to the configuration page currently visible.