background image

Fieldgate FXA720

12 Appendix

Hauser

59

Index

A

Accessories

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  53

Acrobat Reader

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  17

C

Channel

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  39

Commissioning

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  3

Communication parameters

 

 . . . . . . . . . . . . . . . . . . . . . . .  39

Communication port

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . .  15

Communication settings

 

. . . . . . . . . . . . . . . . . . . . . . . . . .  38

Configuration, Fieldgate driver

 

. . . . . . . . . . . . . . . . . . . . .  21

Configuring FXA720 PROFIBUS driver

 

. . . . . . . . . . . . . . .  23

Configuring the web server

 

 . . . . . . . . . . . . . . . . . . . . . . .  29

Connectors

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  9

Conventions

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5

conventions

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  5

D

Declaration of conformity

 

. . . . . . . . . . . . . . . . . . . . . . . . . .  4

Design

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  9

Designated use

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  3

Device designation

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  7

Display elements

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  9

Documentation

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  17

E

Electrical symbols

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  6

E-mail

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  36

Establishing communication

 

. . . . . . . . . . . . . . . . . . . . . . .  18

Ethernet

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  35

Explosion protection

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  6

F

Field Viewer SPV10

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

FieldCare, PROFIBUS DP parameters

 

 . . . . . . . . . . . . . . . .  26

Fieldgate address

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  20

Fieldgate configuration

 

. . . . . . . . . . . . . . . . . . . . . . . . . . .  32

Fieldgate identification

 

. . . . . . . . . . . . . . . . . . . . . . .   33

 47

Fieldgate information

 

 . . . . . . . . . . . . . . . . . . . . . . . .   32

 47

Fieldgate location

 

. . . . . . . . . . . . . . . . . . . . . . . .  32

 33

 47

Fieldgate Viewer SPV10

 

. . . . . . . . . . . . . . . . . . . . . . . . . .  10

Firmware update

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  50

Firmware version

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  47

Function

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

FXA720 PROFIBUS Driver

 

. . . . . . . . . . . . . . . . . . . . . . . .  21

H

Hardware information

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . .  32

Hardware installation

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . .  13

Hardware version

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  47

I

Information & Configuration

 

. . . . . . . . . . . . . . . . . . . . . . . 32

Information&Configuration

 

. . . . . . . . . . . . . . . . . . . . . . . . 47

Installation

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Installing FXA720 PROFIBUS driver

 

 . . . . . . . . . . . . . . . . . 21

Internet address

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

Internet address, Windows 2000

 

 . . . . . . . . . . . . . . . . . . . 55

IP Address

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

IP address

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

 20

 24

L

Live List

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Live list

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  41

 45

Logging on

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  29

 44

M

Making initial contact

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Menu bar

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Mounting

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

N

Nameplate

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Navigation bar

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Network applications

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Network setup

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

New Password

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

O

Operating system

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Operation

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Overview of selected devices

 

 . . . . . . . . . . . . . . . . . .  41

 46

P

P View, PROFIBUS DP parameters

 

 . . . . . . . . . . . . . . . . . . 27

Password

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Power supply

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Power supply units

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Preparing for installation

 

. . . . . . . . . . . . . . . . . . . . . . . . . . 16

PROFIBUS

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

PROFIBUS DP

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

PROFIBUS DP bus parameters

 

 . . . . . . . . . . . . . . . . . . . . . 27

PROFIBUS DP parameters

 

. . . . . . . . . . . . . . . . . . . . . . . . . 26

Profibus setup

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

R

Refresh

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

Retype New Password

 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Summary of Contents for Fieldgate FXA720

Page 1: ...BA030S 04 en 07 07 Product Version 2 00 xx 56004856 Operating Instructions Fieldgate FXA720 Ethernet PROFIBUS DP gateway with Web server 8 ...

Page 2: ......

Page 3: ...ldCare 26 5 3 4 Setting PROFIBUS DP bus parameters in P View 27 5 4 Modifying repairing or removing the application 28 5 4 1 Fieldgate FXA720 PROFIBUS Driver 28 5 4 2 Fieldgate FXA720 documentation 28 6 Configuring the Web Server 29 6 1 Logging on 29 6 2 User interface 30 6 2 1 Menu bar 30 6 2 2 Navigation bar 31 6 2 3 Information Configuration pages 32 6 3 Fieldgate location page 33 6 4 Security ...

Page 4: ...S 04 en 12 04 Single channel version Getting started revised Update of user interface Addition of limit alarms New security set up E mails now possible Chapter 4 revised accordingly Chapter 5 describes web and pass through set up Chapter 7 2 Chapter 7 4 Chapter 7 5 Maintenance user added Chapter 7 6 2 00 xx BA030S 04 en 07 07 Product Java Applets no longer supported Revision of Web server pages Ed...

Page 5: ...r system administrator will be authorised to allocate unique addresses for your Fieldgates Assigning an unauthorised address to a Fieldgate may result in conflicts within your system and the failure of the associated devices 1 3 Operational safety The unit must not be used in explosion hazardous areas The permissible ambient conditions given in the technical data must be complied with Repair Do no...

Page 6: ...omponents AC adapter PROFIBUS stations etc must also meet these requirements To meet the EMC conditions the device must be installed and connected in accordance with the Installation Instructions Warning This is a Class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures FCC This equipment has been tested an...

Page 7: ... File menu With the CTRL key CONTROL key held down press the SHIFT key Keep the CTRL key pressed and press the SHIFT key With the CTRL key CONTROL key held down click the left mouse button Keep the CTRL key pressed and left click the mouse CAPS Details on paths and file names in the text DOKUFMR2XX PDF or WIN HLP Angle brackets Variables CD ROM drive Icon Meaning Note A note highlights actions or ...

Page 8: ...used in drawings to indicate if necessary non explosion hazardous areas Devices located in safe areas stiill require a certificate if their outputs run into explosion hazardous areas Icon Meaning Direct voltage A terminal to which or from which a direct current or voltage may be applied or supplied Alternating voltage A terminal to which or from which an alternating sine wave current or voltage ma...

Page 9: ...PROFIBUS driver supplied with the Setup CD can be used on any computer that is to be used with Fieldgate FXA720 The license agreement is on the Setup CD The software required for start up and commissioning is freely available or is subject to the licensing conditions of its manufacturer Installation of the software on your computer implies that you accept the terms of the corresponding licensing a...

Page 10: ...r Windows and web based applications such as configuration monitoring and visualisation Process data can be monitored with the integrated Web server Fieldgate can also be integrated into system applications via OPC DTM or XML eg OPC for exchanging data with applications such as SCADA HMI OPC clients e g P View SPV200 DTM for exchanging data with FDT frame applications e g FieldCare XML for exchang...

Page 11: ... possible It goes out temporarily during transmission and blinks when Browser clients are connected to the Fieldgate RUN Available for application specific purposes and is off by default FAIL Available for application specific purposes and is off by default DP1 DP2 DP3 Green LEDs that are the token LEDs of the PROFIBUS Master The corresponding LED lights as soon as the master has received the toke...

Page 12: ...applications on line off line data acquisition and display Via XML Fieldgate Viewer SPV10 data acquisition and visualisation Via OPC SCADA HMI OPC clients e g P View data acquisition and visualisation with trends and historian Via DTMs FDT frame applications such as FieldCare asset management Information Configuration or other Information Configuration tool Any other OPC client FDT based or XML HT...

Page 13: ...pplications running on Ethernet are Via OPC SCADA HMI OPC clients e g P View Via DTM Asset management tools based on FDT frames e g FieldCare Via XML Microsoft Office and e Commerce applications Any other OPC client FDT based or XML HTML application Fig 3 3 Typical example of a PROFIBUS DP control network with Fieldgate used in pass through mode Fieldgate FXA720 PROFIBUS DP Segment coupler Segment...

Page 14: ...Service Pack extensions MS Internet Explorer 5 0 with current security updates Netscape Navigator 4 7 with current security updates Opera 6 0 with current security updates Mozilla Firefox 1 0 with current security updates Add on Version Function FieldCare 1 0 FieldCare is Endress Hauser s FDT based Plant Asset Management tool which can be used to configure all devices Add on Version Function P Vie...

Page 15: ...g ducts are at the top and bottom of the unit Ensure that there is a ventilation space of at least 30 mm above and below the device There is no need for a lateral clearance Fig 4 1 Dimensions and clearances for Fieldgate mounting 111 mm 35 mm top hat rail 135 mm 30 mm clearance 30 mm clearance FAIL ON ETH RUN 24VDC COM PROFIBUS DP1 ETHERNET DP1 PROFIBUS DP2 PROFIBUS DP3 DP2 DP3 L M FXA720 ControlC...

Page 16: ...d and must be connected to the protective ground For use in an environment that is highly subject to electromagnetic interference an additional ground connection can be provided at the grounding screw below the ETH connector The power supply is connected to the plug connector via flexible wires with a cross section of 0 75 to 1 5 mm The ground connection wire must have a cross section of 1 5 mm Fu...

Page 17: ...ith up to three PROFIBUS DP channels RS 485 labeled DP1 DP2 and DP3 Each channel is electrically isolated up to a voltage of 500V DC The connecting element is a 9 pin female D sub connector with the following pin assignment Table 4 2 Pin assignment of RS 485 PROFIBUS DP ports Note Please observe the installation guidelines for PROFIBUS devices which are available from the PROFIBUS Trade Organizati...

Page 18: ... Warning The use of IP addresses is strictly controlled Usually your system administrator will be authorised to allocate unique addresses for your Fieldgates Assigning an unauthorised address to a Fieldgate may result in conflicts within your system and the failure of the associated devices 5 1 Preparing for installation 5 1 1 Checking the system requirements Procedure 1 Place the Fieldgate CD ROM...

Page 19: ... with the installation by clicking the Next button 4 To open select Start Programs Endress Hauser Fieldgate FXA720 English Manuals and select the document you require 5 1 3 Adobe Acrobat Reader You require Adobe Acrobat Reader to read the PDF file The current Reader version is supplied on the CD ROM 1 To install select the Component Installation option Then double click on Adobe Acrobat Reader 2 T...

Page 20: ...ocedures for Windows 2000 is described in Chapter 11 Before starting the Fieldgate FXA720 must either be installed in the network connected to a switch hub with a straight cable or be connected directly to the computer with a cross link cable Procedure 1 Right click Start Settings Control Panel Network Connections 2 Right click Local Area Connection Properties Using the left mouse button double cl...

Page 21: ...f your browser and press the Enter key of your computer 5 The browser makes connection with the Fieldgate a User Login window appears Enter the password superb Press Login to display the entry page of the Fieldgate If no connection can be made consult Chapter 12 3 6 After the password has been entered the Fieldgate Web Server opens you will not necessarily see devices at this point ...

Page 22: ...ernet screen enter the IP address given to you by the system administrator in this example 192 168 253 50 Enter the Subnet mask in this example 255 255 255 0 If appropriate enter a Gateway address router firewall connecting LAN to WAN WWW Press Send to download the parameters to the Fieldgate 4 Contact with the Fieldgate may break down at this stage In all cases close the browser 5 Reset the IP ad...

Page 23: ...has already been installed with the Host application e g in connection with FieldCare Overwriting the original will cause the application to malfunction You will be warned during installation if a driver already exists 5 3 1 Installing the driver Procedure 1 Place the Fieldgate CD ROM in your CD ROM drive the Setup menu appears 2 Click on Component Installation to start the software installation p...

Page 24: ...e agreement and check I accept then press Next Print causes the license to be printed out Cancel breaks off the installation procedure 6 Now enter your customer information Press Next to proceed 7 Press Install to start the installation 8 Press Finish to close the wizard ...

Page 25: ... FXA720 icon to open the driver Note If you are using Fieldgate FXA720 with FieldCare the select the PROFIGate driver 2 Select the PROFIBUS DP line to display the general release information 3 Now select the Fieldgate FXA720 line and press Add 4 A symbolic node name for each PROFIBUS DP channel Default value Node 0 can now be entered Click Next to proceed with the configuration ...

Page 26: ...gs should be changed by PROFIBUS specialists only 7 If the Fieldgate is found in the network and is working properly then the Node line will be marked with a green check mark In addition Fieldgate information is displayed The node configuration can be modified from this screen by clicking the Edit button To save the configuration please click Apply 8 For single channel Fieldgates press OK to store...

Page 27: ... address for operation Select Bus 2 or Bus 3 as appropriate 10 Click Finish to accept the default timeout settings and end the configuration Caution Timeout settings should be changed by PROFIBUS specialists only 11 On completion the new node will be added to the network tree Press Apply to store the configuration Note the screenshot shows the two channel version 12 When all channels have been con...

Page 28: ...bed in the extended Getting Started manual supplied on the FieldCare CD ROM 2 Add the Communication device PROFIdtmDPV1 this is the Fieldgate FXA720 CommDTM Right click on the node in our example it has been re named Fieldgate FXA720 and select Configuration The CommDTM for Fieldgate FXA720 appears 3 The board names are automatically taken from the node names set in the PROFIGate driver Select the...

Page 29: ...ntrolCare P View the PROFIBUS DP baudrate is set in the PROFIBUS OPC server Procedure 1 Start the OPC server from the Control Panel and set it up as decribed in the P View manual Click on the Fieldgate node Master to open the configuration window 2 In the Basic folder set Station name Station address Baudrate Master Class 2 If necessary check Read All Slaves and press Quickstart to scan the bus 3 ...

Page 30: ...the installation 3 To repeat the installation procedure and install the Fieldgate application again select Repair Now select the components you desire and press Next to install Press Finish to complete the installation 4 To remove the Fieldgate application entirely select Remove Press OK to confirm 5 4 2 Fieldgate FXA720 documentation If you have already installed the Fieldgate application you can...

Page 31: ... Fieldgate Security Setup Chapter 6 5 provides more information on setting up passwords etc Table 6 1 Fieldgate user roles and rights Logging off In specialist mode click on the Logout link then close the internet browser In user mode close the internet browser Role User name Default password Rights Administrator admin super Can access Fieldgate in both User and and Specialist mode Can configure n...

Page 32: ...erview For a large network this means that the first build up of the overview may take some time The user interface consists of the following elements Menu bar belongs to the web browser installed Navigation bar Information Configuration pages 6 2 1 Menu bar Example of how the menu bar is displayed in MS Internet Explorer The IP address of the Fieldgate is entered in the address field of the Inter...

Page 33: ...e Fieldgate according to channel XML Export Exports all information about Fieldgate and the devices connected to it in XML format Function Description Refresh Updates the current display with fresh information from the Fieldgate Logout Changes to User Mode Endress Hauser Calls the Endress Hauser Fieldgate Web site Live List Displays all devices connected to the Fieldgate and allows them to be conf...

Page 34: ...de Switch to User Mode as appropriate and when prompted by entering the corresponding password see Chapter 6 1 Fieldgate Information The Fieldgate Information page User Mode provides a read only view of the Fieldgate Location and Hardware Information Fig 6 5 Fieldgate Information page Fieldgate Configuration The user information on the Fieldgate Location page can be edited in Specialist mode Addit...

Page 35: ...w page in the header of your browser in the XML file and the header of the e mail in preparation Note Please note the characters which are permitted and not permitted for defining the Fieldgate identification name of the Fieldgate Permitted characters are Letters a z and A Z without taking case into account Numbers 0 9 Special characters such as period and minus not however as the first character ...

Page 36: ...Press Information Configuration then Security Setup The Security Setup screen appears 3 Enter the parameters you require in the screen their significance is described in the table below Administrator rights allow access to all Fieldgate setup parameters Maintenance rights allow access to all Fieldgate setup parameters except security Executive rights allow access for viewing parameters only A full...

Page 37: ...get an IP address from your Internet provider or your system administrator If you change the IP address in this screen Close the connection it may break off automatically Use the new address in your browser to call up the Fieldgate If appropriate enter the new IP address in the PROFIBUS driver of any host application see Chapter 5 3 Network parameters Table 6 6 Ethernet network parameters Paramete...

Page 38: ...ill be accepted from other sender addresses Alarms E Mail Address Enter the recipient of the alarm mails here e g name company co uk Alarm notifications are sent in accordance with the settings made in the E Mail on Alarm column of the device details page see Chapter 6 4 If the Fieldgate is restarted when alarm violations are present e mails will be resent although the an alarm notification has al...

Page 39: ...scription Time Server Enter the IP address of the time server here You can find information on public NTP servers under http www eecis udel edu mills ntp servers htm or http www google de search q public ntp servers Protocol Set the protocol used by the time server here SNTP Standard port 123 MAN Manual time setting timing is restarted with settings entered in Set time The time server operator can...

Page 40: ...P View or the CommDTM PROFIdtmDPV1 FieldCare 6 6 1 Communication settings Procedure 1 If not already selected press Switch to Specialist Mode and log in as administrator or maintenance engineer 2 Press Information Configuration then PROFIBUS Setup The following screen appears the number of channels depends on the Fieldgate 3 Set up each channel by entering or ticking the parameters see Table 6 9 T...

Page 41: ...Bit of a telegram to the sending of the first Bit of a following telegram Max StationDelay Response Time Longest time period that must elapse before a Sender Requestor may send a further query telegram Greatest time period between receipt of the last Bit of a telegram to the sending of the first Bit of a following telegram The Sender Requestor Master must wait at least for this time period after t...

Page 42: ...not reproduce the live lists of channels that are being used in pass through mode Scan Cycle Time off No devices are shown for these channels Parameter Description Scan Cycle Time Interval at which the devices on the channel are to be scanned Select a scan time from the drop down menu for all channels that are being used by the Internet browser Web server Check that the setting is off default for ...

Page 43: ...log in as administrator or maintenance engineer 2 By default the Live List automatically appears 3 Click on the Device Tag in column Address Device Tag to reveal the details of the device Setup each device function block according to the descriptions in Table 6 6 After the parameters have been set up for each device press Send to download them 4 Now click the Device Tag in header top left to view ...

Page 44: ... are not consistant Note The limit status applies to the limit values set in the web server It has nothing to do with any limits set within the device itself Limit Allows four limits to be set in the web server on the parameter concerned HH High high limit an alarm is set when measured value moves above the high high limit H High limit an alarm is set when the measured value moves above the high l...

Page 45: ...IBUS data types Concrete information on these topics can be found in the operating instructions of the field devices concerned In Specialist Mode a click on the Device Details switches over to the configuration page for slot index entries Depending upon requirement this page allows the value status and if necessary the engineering units of parameters other than those offered by default to be read ...

Page 46: ...he the devices and Fieldgate is viewed in User Mode 7 1 Logging on Procedure 1 Enter the Fieldgate IP address your web browser after connection has been made you will be asked to log on 2 Enter your password in the Password field default password superb 3 The Fieldgate home page is now shown with the Overview of Selected Devices ...

Page 47: ... 1 By clicking the mouse over the Address link you can change from the Live List to the Overview 2 By clicking the mouse over the Device Tag link you can change from the Live List to the Device Details Live list parameters Table 7 1 Parameters in Live List view page Parameter Description Show in Overview Devices checked in this column will appear in the Overview Address Device Tag PROFIBUS address...

Page 48: ...l status Point Name The name of the parameter that is being monitored at the assocation address Current value The current value of the parameter with parameter status and time stamp Limit The status of the limit values set in the Fieldgate for the parameter with time when last status change occured OK within alarm limits HH High high alarm the measured value is above the high high limit H High ala...

Page 49: ...e Tag Identification Fieldgate tag number name Fieldgate Location Place where Fieldgate is installed Installation date Date of installation maintenance Remarks User information about Fieldgate Hardware Information Product Designation Complete product designation of the Fieldgate see nameplate Hardware Version Fieldgate hardware version number Serial Fieldgate serial number Web Server Version Versi...

Page 50: ...ted devices to be downloaded to your computer for use in Office or other applications 1 Press XML Export The parameters are downloaded into a separate page from where they can be copied and pasted More information on the XML elements can be found in the Appendix Chapter 12 2 2 Note the web address this can then be accessed by your browser as a read only page no values can be changed without prior ...

Page 51: ...eb browser e g Internet Explorer with the F5 key It does not initiate a bus scan 7 6 2 Endress Hauser function With the Endress Hauser function you go directly to the Fieldgate homepage on the Endress Hauser internet site You require Internet access for this There is no charge for displaying the page Note This page can also be called directly via Internet brower by entering the following address w...

Page 52: ...nload Firmware and Restart to download the firmware to the Fieldgate Caution Do not interrupt the download process this will result in a malfunction that can be repaired by the manufacturer only 5 Select the PROFIBUS Setup page and press Send to download the PROFIBUS settings and Scan settings 6 If you are upgrading from version 1 00 21 to 1 01 xx go to the Security Setup page and define a mainten...

Page 53: ...comes a Master Class I In case of a configuration tool all acyclic data inititated by the configurator is forwarded to devices through the Fieldgate as Master Class II services For example PROFIBUS OPC Server normally behaves as Master Class I and CommDTMs as Master Class II What parameters are available for configuration via web server Chapter 6 describes the Fieldgate parameters that can be conf...

Page 54: ...proceed with point 3 No check the cable or connection to Fieldgate and PC Network 3 Open the DOS prompt Start Run cmd 4 Enter ping 192 168 252 1 Do you get the answer 192 168 252 1 Bytes 32 Yes The connection is OK Check your browser settings If a proxy server is used try to bypass the IP address 192 168 254 1 No There is no connection to the Fieldgate 5 Check if Fieldgate s IP and Subnet mask are...

Page 55: ...Fieldgate FXA720 10 Accessories Endress Hauser 53 10 Accessories 10 1 E H power supply units Product Description SXP 100 Standard power supply 5A 24 VDC ...

Page 56: ... current 3A Dimensions W x H x D 111 x 135 x 111 mm multi channel version 46 5 x 135 x 111 mm single channel version Mounting TS35 DIN carrier rail EN 50022 Weight approx 0 9 kg 0 3 kg Protection class III Degree of protection IP 20 Degree of contamination 1 Ambient temperature during operation 0 C to 55 C Ambient temperature for storage 20 C to 70 C Relative air humidity max 90 at 25 C non conden...

Page 57: ...n For the following instructions under Windows 2000 you require administrator rights Contact your system administrator Procedure 1 Right click on the desktop icon My Network Places and select Properties Right click Local Area Connection Properties 2 Using the left mouse button double click Internet Protocol TCP IP ...

Page 58: ...ser 3 Now you can enter change the values and click OK to confirm 4 Start the web browser e g Internet Explorer 5 Now enter the same address e g 192 168 253 1 in the address field of your browser The Fieldgate FXA720 password window is displayed ...

Page 59: ...block PHYSICAL_BLOCKS End physical blocks FUNCTION_BLOCKS Start function blocks FUNCTION_BLOCK type fb_input_analog Start function block TAG FB0011_fb_input_analog TAG Point name LIMITSIGN LO LIMITSIGN Limit status HH HI OK LO LL OUT 0 818859 OUT Current value STAMP_DATE_VAL 20070621 STAMP_DATE_VAL Date stamp of current value STAMP_TIME_VAL 170445 STAMP_TIME_VAL Time stamp of current value STAMP_D...

Page 60: ...e set individually If a value is entered that is above the limit the highest possible value will be set If a value is entered that is below the limit the lowest possible value will be set Table 12 1 PROFIBUS bus parameter ranges Parameter Valid range tsl 37 16383 min tdsr 11 1023 max tdsr 37 1023 tqui 0 239 tset 1 255 ttr 256 16777215 γ 1 100 hsa 1 126 station address 0 126 ...

Page 61: ...47 Fieldgate location 32 33 47 Fieldgate Viewer SPV10 10 Firmware update 50 Firmware version 47 Function 8 FXA720 PROFIBUS Driver 21 H Hardware information 32 Hardware installation 13 Hardware version 47 I Information Configuration 32 Information Configuration 47 Installation 3 Installing FXA720 PROFIBUS driver 21 Internet address 55 Internet address Windows 2000 55 IP Address 35 IP address 18 20 ...

Page 62: ...ndex configuration 43 Software Installation 16 Specialist Mode 32 System architecture 10 System requirements 12 16 T Technical data 54 Time server 37 Trouble shooting 51 U User interface 30 User login 19 User Mode 32 44 User Name 34 User roles 29 V Viewing Information 44 W Web browser 18 Web Server 29 Web based applications 10 Wiring 14 X XML export 48 ...

Page 63: ......

Page 64: ...www endress com worldwide ...

Page 65: ...12 Appendix Fieldgate FXA720 63 Endress Hauser ...

Page 66: ...Fieldgate FXA720 12 Appendix Endress Hauser 64 ...

Reviews: