background image

FieldCare

Fieldgate SFG500

16

Hauser

4.1.7

Store the project

1. Right-click on the 

File

 menu and select 

Save

– The 

Save Project As

 window appears

– Enter a name for the project and press 

Save

2. The project can now be opened from the

 Existing

 tab in the project window that opens 

when FieldCare is started

Summary of Contents for Fieldgate SFG500

Page 1: ...lutions Services BA00071S 04 en 03 13 Product Version 1 01 xx 71213933 Operating Instructions Fieldgate SFG500 Operation as Access Point 8 Power Run Failure RS485 LAN 1 LAN 2 PB DP PB Err Reset SFG500 LAN 1 LAN 2 ...

Page 2: ......

Page 3: ...rchitecture 17 4 2 2 Create a FieldCare project 18 4 2 3 Add the SFGNetwork CommDTM 18 4 2 4 Scan for Fieldgate SFG500 18 4 2 5 Scan for devices 19 4 3 Segment with Siemens link 20 4 3 1 Architecture 20 4 3 2 Create a FieldCare project 21 4 3 3 Add the SFGNetwork CommDTM 21 4 3 4 Scan for Fieldgate SFG500 21 4 3 5 Scan for the Coupler Link 22 4 3 6 Scan for devices 23 4 4 Segment with Stahl Remote...

Page 4: ...obe Systems Incorporated All other brand and product names are trademarks or registered trademarks of the companies and organizations in question Product version Manual Changes Remarks 1 00 xx BA00071S 04 en 01 11 Original manual 1 00 xx BA00071S 04 en 02 12 Editorial Chapter 3 IP LAN1 10 126 84 100 Chapter 5 1 1 Chapter 5 3 4 Chapter 5 3 5 New DTM function PROFIBUS Scan Range New DTM function Set...

Page 5: ...ed manuals personnel must be authorised and suitably qualified 1 3 Operational safety When using Fieldgate SFG500 as an Access Point the instructions in Chapter 1 3 of BA0070S 04 en Fieldgate SFG500 Installation and Commisioning shall be observed 1 4 Supplementary documentation Table 1 1 indicates the documents planned and realized containing safety relevant information installation commissioning ...

Page 6: ...xplosion hazardous areas Devices located in and wiring entering areas with the designation explosion hazardous areas must conform with the stated type of protection Safe area non explosion hazardous area Symbol used in drawings to indicate if necessary non explosion hazardous areas Devices located in safe areas still require a certificate if their outputs run into explosion hazardous areas Icon Me...

Page 7: ...ss point The control network comprises one or more PLCs or DCSs and one or more PROFIBUS DP segments Connected to the PROFIBUS DP segment are PROFIBUS DP slaves Remote I Os and segment couplers or links Through its Ethernet port LAN1 Fieldgate SFG500 allows FieldCare access to access a PROFIBUS DP segment If there is more than one segment in the PROFIBUS DP network a separate Fieldgate SFG500 is r...

Page 8: ...nistration rights for your computer and network You have an set of IP addresses that have been authorized by your IT department Any proxy server for your Internet Browser is disabled Fieldgate SFG500 is supplied with the following default IP addresses LAN1 10 126 84 100 LAN2 192 168 253 1 Fieldgate SFG500 acts as a DHCP server on the LAN2 service interface and will automatically assign any compute...

Page 9: ...Explorer 1 Right click on the Internet Browser icon on your desktop and select Properties The Properties dialog opens 2 Now click on the tab Connections followed by the button LAN Settings The Local Area Network LAN Settings dialog appears 3 Disable the proxy server by clicking on the check box The x disappears and the proxy fields go grey 4 Press OK to confirm you settings Press OK to close the P...

Page 10: ...eldgate SFG500 6 Click on Logout above right to secure the web page again 3 2 2 IP address of the FieldCare computer Before FieldCare can use Fieldgate SFG500 to connect to the PROFIBUS network the computer on which it is running must be given an address in the same domain 1 Proceed as described in Appendix A and give your computer a fixed address in the same address domain as that of Fieldgate SF...

Page 11: ...uctions 3 3 2 Update the FieldCare DTM catalog Before it can be used the SFGNetwork DTM must be integrated in the FieldCare DTM Catalog NOTE For FieldCare Standard and Professional administrator rights are required to update the DTM catalog if these are activated 1 Start FieldCare and if necessary log on as administrator 2 In the Start Up Screen dialog press Continue and in the FieldCare dialog pr...

Page 12: ...the PROFIBUS DP segment The segment itself is connected to a PLC or DCS which acts as Class 1 master PROFIBUS PA devices are connected to the network via the coupler Fig 4 1 Architecture for single segment To see all the devices on the PROFIBUS DP PA segment FieldCare requires SFGNetwork DTM All Device DTMs PLC DCS PB Master Class 1 DP PA Coupler Control Network LAN 1 Ethernet FieldCare PROFIBUS D...

Page 13: ...r 11 4 1 2 Create a FieldCare project 1 Open FieldCare by a double click on its desktop icon If necessary enter the user name and password 2 Press Continue to close the introductory page 3 Press Open to create a project 4 A project is created ...

Page 14: ...user 4 1 3 Add the SFGNetwork CommDTM 1 In the network view right click on Host and select Add Device 2 The CommDTM catalog opens Select SFGNetwork Press OK to add the CommDTM to the Host 3 The SFGNetwork CommDTM is added to the Network view ...

Page 15: ...select Create Network 3 FieldCare searches for any SFG500s in the Ethernet network and adds them to the network view 4 If only one is found it connects and opens the SFG500 CommDTM 5 If no DTM is found it is possible that the UDP ports are blocked Either unblock as described in Appendix B you will need administrator rights Or add the CommDTM manually right click on SFG500 Network node Add Device a...

Page 16: ...nd are added to the network If any of the devices has a DTM of quality less than 1 the Scanning Result dialog opens and OK must be pressed before the devices are added to the network 3 If only one device is found its DTM will be opened automatically If more than one device is found and the Connect after scanning option is selected in Extras the message below must be acknowledged with OK and the de...

Page 17: ...e you want to open and select Connect The communication arrows turn green to indicate that it is online 2 Right click on the node of the device again and select Online Parametrize 3 The DTM of the selected device is opened The device can now be configured according to the instructions in its operating manual ...

Page 18: ...ore the project 1 Right click on the File menu and select Save The Save Project As window appears Enter a name for the project and press Save 2 The project can now be opened from the Existing tab in the project window that opens when FieldCare is started ...

Page 19: ...ments via couplers Fig 4 1 Architecture for multiple segments To see all the devices on the PROFIBUS DP PA segment FieldCare requires SFGNetwork DTM All Device DTMs PLC DCS PB Master Class 1 Control Network LAN 1 Ethernet FieldCare PROFIBUS DP Access Points PB Master Class 1 PB Master Class 1 PB Master Class 1 PB Master Class 1 Segment 1 Segment 2 Segment 3 Segment 4 Segment 5 RS485 LAN 1 LAN 2 PB...

Page 20: ...d to the Network view 4 2 4 Scan for Fieldgate SFG500 NOTE The dialogs for this procedure are identical to those in Chapter 4 1 4 1 Right click on the SFGNetwork node and select Connect to put the CommDTM online The Connection arrows turn green 2 Right click on the SFC500 Network node and select Create Network 3 FieldCare searches for any SFG500s in the Ethernet network If the Connect after scanni...

Page 21: ...ore the devices are added to the network If more than one device is found and the Connect after scanning option is selected in Extras the Connect after scanning message below must be acknowledged with OK All devices found are then added to the network view If only one device is found and the Connect after scanning option is selected in Extras default setting FieldCare adds it to the network view c...

Page 22: ...OFIBUS PA devices are connected to the network via the Siemens Coupler Link Fig 4 1 Architecture for Siemens coupler link To see all the devices on the PROFIBUS DP PA segment FieldCare requires SFGNetwork DTM Licensed Trebling and Himstedt CommDTM DP PA link All Device DTMs PLC DCS PB Master Class 1 Siemens Link DP PA Coupler PROFIBUS PA Control Network LAN 1 Ethernet FieldCare PROFIBUS DP Segment...

Page 23: ... add the CommDTM to the Host 3 The SFGNetwork CommDTM is added to the Network view 4 3 4 Scan for Fieldgate SFG500 NOTE The dialogs for this procedure are identical to those in Chapter 4 1 4 1 Right click on the SFGNetwork node and select Connect to put the CommDTM online The Connection arrows turn green 2 Right click on the SFC500 Network node and select Create Network 3 FieldCare searches for an...

Page 24: ...e Network Scanning result dialog opens Press OK to add the DP PA Link CommDTM to the network 4 The DP PA Link CommDTM is added to the Network view If only one device is found and the Connect after scanning option is selected in Extras default setting FieldCare adds it to the network view connects and opens the DTM If more than one device is found and the Connect after scanning option is selected i...

Page 25: ...gment to which the DP PA Link is connected for devices The Create Network Scanning result dialog opens Press OK to add the devices to the network 4 If the Connect after scanning option is selected in Extras the message below must be acknowledged with OK as more than one device has been found 5 The devices are added to the Network view 6 The Device DTMs can be opened and the project stored as descr...

Page 26: ...20 mA HART devices are connected point to point to the Stahl Remote I O which in turn is connected to the PROFIBUS DP segment Fig 4 1 Architecture for Stahl remote I O To see all the devices on the PROFIBUS DP PA segment FieldCare requires SFGNetwork DTM Licensed Stahl CommDTM CPM 9440 All PROFIBUS Device DTMs All HART Device DTMs PLC DCS PB Master Class 1 DP PA Coupler Control Network LAN 1 Ether...

Page 27: ...K to add the CommDTM to the Host 3 The SFGNetwork CommDTM is added to the Network view 4 4 4 Scan for Fieldgate SFG500 NOTE The dialogs for this procedure are identical to those in Chapter 4 1 4 1 Right click on the SFGNetwork node and select Connect to put the CommDTM online The Connection arrows turn green 2 Right click on the SFC500 Network node and select Create Network 3 FieldCare searches fo...

Page 28: ...e Network Scanning result dialog opens Press OK to add the Stahl CPM 9440 CommDTM to the network 4 The CPM 9440 CommDTM is added to the Network view If only one device is found and the Connect after scanning option is selected in Extras default setting FieldCare adds it to the network view connects and opens the DTM If more than one device is found and the Connect after scanning option is selected...

Page 29: ...nect after scanning option is selected i n Extras default setting FieldCare adds it to the network view connects and opens the DTM If more than one device is found and the Connect after scanning option is selected in Extras the Connect after scanning message below must be acknowledged with OK All devices found are then added to the network view 5 The Device DTMs can be opened and the project store...

Page 30: ...ss Enter The connection is made and the IP address and Device Tag are displayed IP Address The IP Address entry box is enabled Enter the IP address of the associated device and press Enter The connection is made and the serial number and Device Tag are displayed Device Tag The Device Tag entry box is enabled Enter the device tag of the associated device and press Enter The connection is made and t...

Page 31: ...ecessary to configure the proxy server 1 The proxy server is configured in the advanced settings of the configuration dialog These are selected by enabling the tree view of the dialogue with the leftmost button in the toolbar 2 The options in the drop down menu are as follows Parameter Meaning automatic default First the system settings are used If this does not work option no Proxy Server is used...

Page 32: ...eady done right click on the SFG500 node and select Connect to put the Fieldgate DTM online 2 Right click on the SFG500 node and select Additional Functions Embedded Web Server The PROFIBUS Live List window opens 3 Navigate through the menus by clicking on the Tabs or the sub menu items The number of tabs that appear depends upon whether Fieldgate Module SFM500 is in use and the functions that it ...

Page 33: ... window opens 3 The various elements have the following significance Element Meaning Overview table Indicates the number of devices on the bus together with their type and status Green Device in cyclic data exchange status OK Yellow Device in cyclic data exchange has diagnostic message Orange Device failed to enter into cyclic data exchange Grey Device is present but not in cyclic data exchange Bl...

Page 34: ...rey Device is present but not in cyclic data exchange Blue Fieldgate SFG500 Show Grid View Show List View Toggles between a grid and list view of the connected devices Live list Slave Slave ID in PROFIBUS live list Saaa aaa PROFIBUS address Ident Slave device type Device Type Manufacturer s device type identification Serial No Manufacturer s serial number of the slave Tag Tag No of the slave Statu...

Page 35: ...message since last restart of monitor FAIL Device has failed since last restart of monitor Init Indicates the number of device initializations since the last restart of monitor Diag Indicates the number of diagnostic messages since the last restart of monitor Last Diagnosis Time Indicates the time of the last diagnostic message issued by the device If there has been no message the time of the last...

Page 36: ...ns 3 The parameters have the following significance Parameter Description Configuration Mode Auto Mode Fieldgate SFG500 detects the PROFIBUS parameters and sets its own address The detected PROFIBUS parameters are displayed Overwriting is disabled Passive Mode Fieldgate SFG500 listens to the bus but does not enter traffic as Master Class 2 FieldCare cannot be used with this mode Manual Mode Writin...

Page 37: ...ipt of the last Bit of a telegram to the sending of the first Bit of a following telegram The Sender Requestor Master must wait at least for this time period after the sending of an unacknowledged telegram e g Broadcast only before a new telegram is sent Quiet Time Time delay that occurs for modulators Modulator trip time and Repeaters Repeater switch time for the change over from sending to recei...

Page 38: ...dow opens 3 Select the address of the device whose address must be changed from the Current Address drop down menu 4 Select the address the device should be given in the New Address drop down menu 5 Press Apply to write the change of address to the device Pressing Cancel will discard all changes and leave the device with its old address A possible reason for a failure to change an address is that ...

Page 39: ...e parameters will be adjusted during the commissioning of Fieldgate SFG500 as described in Chapter 7 2 6 of Operating Instructions BA00070S 04 en Fieldgate SFG500 Installation and Commissioning The firmware update is described in Chapter 8 2 3 of the same manual Information tab The Information tab displays the information stored on the Electronic nameplate of Fieldgate SFG500 and where of Fieldgat...

Page 40: ...uttons and parameters have the following significance Parameter group Meaning Logging tab Shows the communication log Starts automatically on call up After a log has been cleared press the Start button to restart the logging Settings tab Sets the filters for the events to be logged Information logs all information messages Warning logs all warning messages Error logs all error messages Comment Log...

Page 41: ...ess must be changed from the Current Address drop down menu 3 Select the address the device should be given in the New Address drop down menu 4 Press Apply to write the change of address to the device Pressing Cancel will discard all changes and leave the device with its old address A possible reason for a failure to change an address is that the device is locked 5 After an address change the devi...

Page 42: ...uttons and parameters have the following significance Parameter group Meaning Device Name Shows the device and firmware version associated with the DTM Device Tag Shows the device tag of each device connected to the selected Fieldgate SFG500 To change a device tag enter the new designation then press Update Address Shows the PROFIBUS address of each device connected to the selected Fieldgate SFG50...

Page 43: ...of the SFG500 DTM 1 Right click on the SFG500 node and select Additional Functions Help The SFG500 Help opens 2 Navigate to the topic of interest 5 3 5 About About gives information about Fieldgate SFG500 and its Device DTM 1 Right click on the SFG500 node and select Additional Functions About The SFG500 About window opens ...

Page 44: ... are enabled on the router see also Appendix B UDP 60020 from SFG500 network to PC TCP 60010 in both directions No connection after manual connect additional remedies Check any error messages in FieldCare Check the configuration of the CommDTM is entered IP address Tag Serial number correct 4 SFG500 DTM cannot find PROFIBUS device s No connection Check all PROFIBUS connections Check that device is...

Page 45: ...y be set up to accept an IP address from a DHCP server If you computer is used in a control system however it is possible that it has a fixed address In this case in order to connect to Fieldgate SFG500 s LAN2 port proceed as follows Procedure for Windows XP 1 Right click Start Settings Control Panel Network Connections 2 Right click Local Area Connection Properties 3 Using the left mouse button d...

Page 46: ...ow Resetting the fixed IP address After the Fieldgate SFG500 has been set up you can reset your computer to its old address as follows 7 Repeat Steps 1 to 3 of the above procedure 8 In the Internet Protocol TCP IP Properties dialog select the option Use the following IP address Re enter the settings that you noted at Step 4 9 Now click OK to confirm your selection and close the dialog Press OK to ...

Page 47: ... to perform this task 1 Press Start Control Panel Windows Firewall 2 Press the Exceptions tab to add the exceptions on two main levels Add program specify which applications are able to respond to unsolicited requests Add Port specify that the firewall should allow TCP traffic at ports used by the servers see Table 4 1 below 3 In the General tab select the On recommended radio button to switch on ...

Page 48: ...Changing a computer s IP properties Fieldgate SFG500 46 Endress Hauser For your notes ...

Page 49: ...Fieldgate SFG500 Changing a computer s IP properties Endress Hauser 47 For your notes ...

Page 50: ...17 PROFIBUS Live List 30 PROFIBUS Monitor 33 PROFIBUS Settings 34 S Safety 3 Settings tab 37 SFG500 DTM About 41 Additional Functions 38 Communication log 38 Configuration 28 Diagnosis 30 Help 41 PROFIBUS live list 38 Profibus parameters 38 Set Device Address 39 Set DTM Address 40 SFGNetwork DTM 9 10 17 20 24 Siemens link 20 Slave Settings 36 Stahl Remote I O 24 T Trebling and Himstedt CommDTM DP ...

Page 51: ......

Page 52: ...www addresses endress com ...

Reviews: