Fieldgate SFG500
DTM for Fieldgate SFG500
Hauser
31
5.2.1
PROFIBUS live list
The PROFIBUS live list shows all devices that can be seen by the selected Fieldgate SFG500
when it is listening to the bus. If the listener was active during the initialization of the slaves,
the slave ID is shown.
Grid View
1. Right-click on the SFG500 node and select
Additional Functions =>Embedded Web
Server
then click on the
Network
tab.
2. Click on
PROFIBUS live list
– The SFG500 PROFIBUS Live List window opens:
3. The various elements have the following significance:
Element
Meaning
Overview table
Indicates the number of devices on the bus, together with their type and status
• Green: Device in cyclic data exchange, status OK
• Yellow: Device in cyclic data exchange, has diagnostic message
• Orange: Device failed to enter into cyclic data exchange
• Grey: Device is present, but not in cyclic data exchange
• Blue: Fieldgate SFG500
Show List View/
Show Grid View
Toggles between a grid and list view of the connected devices
Live list matrix
Indicates the type and PROFIBUS address of the slave
• Mxxx: master with PROFIBUS address xxx
• Syyy: slave with PROFIBUS address yyy
• Colour code: as in overview