FieldGate SWG50
Mounting
Hauser
11
4
Hauser nameplate
4.2.2
Manufacturer's address
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstraße 8
32825 Blomberg
Germany
www.phoenixcontact.com
4.3
Storage and transport
Always use the original packaging when transporting the product.
4.3.1
Storage temperature
–40 to 85 °C
5
Mounting
5.1
Mounting requirements
The device must be installed in a housing that has a minimum protection rating of IP54 as per
EN/IEC 60079-15. The device must be used only in areas with a maximum pollution degree of
2, as defined in EN/IEC 60664-1. The device can be installed in Zone 2 hazardous areas.
Routing and remote installation of the antenna must comply with the relevant site regulations
when installed in unclassified Zone 2 or Class I, Division 2 hazardous areas. Otherwise, the
antenna must be installed within the end-use housing.
A remote antenna can be mounted outside a cabinet. If there is a risk of lightning, install
lightning/EMP protection between the gateway and the remote antenna.
5.2
Mounting the device
The FieldGate SWG50 is mounted on an NS 35 mounting rail. To prevent the device from
slipping, end clamps must be mounted on both sides. The device can be mounted either
horizontally or vertically. The modules are mounted on the mounting rail from left to right.