Caching commands
The FieldGate SWG50 stores a number of commands in the cache. The validity of the stored
data depends on the
Stale Data Timer
Command
Description
3, 778
These commands are used to fill the
Devices
page in the web server and in the Modbus
register. It is expected that most field devices will burst these commands. The gateway
generates a request to update this cached data if it is older than 1/3 of the
Stale Data
Timer
interval. For this reason, the "Stale Data Timer" interval should be set to three
times the burst rate of the field devices.
If the burst rate of the field devices is one minute, the "Stale Data Timer" interval
should be set to three minutes.
1, 2, 9, 42, 48, 76, 89, 93,
95, 512, 769, 779, 781,
796, 798, 804, 808, 810,
817, 822, 833, 1793, 1794
These commands are cached by the gateway. If this data is older than the
Stale Data
Timer
interval, the gateway forwards a request to the field device and renews the cached
data.
0, 7, 8, 11, 12, 13, 14, 15,
16, 20, 21, 35, 74, 75, 84,
101, 105, 774, 776, 778
These commands are cached by the gateway and regarded as "static". They are updated
only if an update is triggered by a HART command.
The receipt of a CMD 22 (Write Long Tag) response generates a CMD 20 (Read
Long Tag) request.
0, 48
If these commands are sent from a HART IP client to a field device, the cached value is
bypassed and a request is sent directly to the field device.