Operation options
FieldGate SWG50
24
Hauser
Field
Description
Device ID
Identification number of the WirelessHART device
Device Tag
Long tag of HART device.
Long tags are supported only from HART 6. Older devices, such as HART 5 devices, must be
labeled via the
Message
field. For a HART 5 device connected in a WirelessHART network,
the WirelessHART gateway emulates the long tag with the
Message
field.
MAC Address
MAC address of WirelessHART device or adapter.
Status
Device status
PV/SV/TV/QV
Displays the process variables of the HART device.
Battery Life
Displays the expected remaining life of the battery that powers the devices.
65535 indicates that the device is receiving power from a mains supply or is waiting for the
device to provide information regarding the battery life.
Neighbours
Number of neighbors with which a WirelessHART device can communicate in the mesh.
Timestamp
Time at which data was last updated. Format: hh:mm
Latency
Time required to respond to all data requests or to update the data (measured in seconds).
Bandwidth
Available bandwidth for the device in question.
Joins
The frequency with which a device was connected to the gateway (since the gateway was restarted)
Active Pipe
Indicates the status of the pipe for a device
Fast Pipe Control This function can be used to enable or disable the fast pipe function for a device.
Deleting the device
Only devices that are not connected can be removed from the list of devices. To delete an
active device, switch off the device and wait until the status column indicates that the
device is no longer connected.
1. Click the device with the right mouse button.
2. Confirm the delete option.
Editing the Slave ID
1. Click the
Edit Slave IDs
button.
2. Enter the new ID number.
3. Click
OK
.
Changes are saved; this may take several minutes.
7.1.8
Adding a device
If a device is added to the network, the FieldGate SWG50 issues several commands.