FieldGate SWG50
System integration
Hauser
27
Gateway polling address
1. Make any necessary changes.
2. Click
Update
.
HART IP
1. Make any necessary changes.
2. Click
Submit
.
A restart notification appears. The changes are applied following a restart.
8
System integration
8.1
Modbus TCP
8.1.1
Condensed Modbus mapping
Condensed Modbus mapping is available when using Modbus device ID 254 in conjunction
with the IP address of the FieldGate SWG50.
Modbus address
Variable
Read/Write
Type
49996
Gateway status register
Read
Integer
49997
WirelessHART device count (includes any disconnected)
Read
Integer
49998
Total Device Count (includes wired sub-devices)
Read
Integer
49999
Live Device Count (anything currently connected)
Read
Integer
4xxx0
PV for Device ID xxx (Float) (MSW)
Read
Float
4xxx12
PV for Device ID xxx (Float) (LSW)
Read
Float
4xxx2
SV for Device ID xxx (Float) (MSW)
Read
Float
4xxx3
SV for Device ID xxx (Float) (LSW)
Read
Float
4xxx4
TV for Device ID xxx (Float) (MSW)
Read
Float
4xxx5
TV for Device ID xxx (Float) (LSW)
Read
Float
4xxx6
QV for Device ID xxx (Float) (MSW)
Read
Float
4xxx7
QV for Device ID xxx (Float) (LSW)
Read
Float
4xxx8
Battery life for Device ID xxx
Read
Integer
4xxx9
Number of WirelessHART neighbors
Read
Integer
1)
A value of 0 indicates a "good" status
2)
xxx stands for the device ID from the web server device table
Summary of Contents for FieldGate SWG50