System integration
FieldGate SWG50
28
Hauser
8.1.2
Expanded Modbus mapping
HART command Type
Memory address
Device variable
Register count
0
Read
4000 (2 bytes)
Expanded device type code
17
40001
Number of preambles required for request
message from client to device
40002
HART protocol major revision number
40003
Device revision level
40004
Software revision level
40005
Hardware revision level
40006
Physical signaling code
40007
Flags
40008 - 40009 (3
bytes)
Device ID
40010
Minimum number of preambles to be sent
with response message from device to
client
40011
Maximum number of device variables
40012 (2 bytes)
Configuration change counter
40013
Extended field device status
40014 (2 bytes)
Manufacturing identity code
40015 (2 bytes)
Private label distributor code
40016 (2 bytes)
Device profile
1
Read
40017
Primary variable units
3
40018 - 40019 (float) Primary variable
2
Read
40020 - 40021 (float) Primary variable loop current
4
40022 - 40023 (float) Primary variable percent of range
3
Read
40024
Secondary variable unit code
9
40025 - 40026 (float) Secondary variable
40027
Tertiary variable unit code
40028 - 40029 (float) Tertiary variable
40030
Quaternary variable unit code
40031 - 40032 (float) Quaternary variable
6
Write
40036
Polling address
2
40037
Loop current mode
8
Read
40038
Primary variable classification
4