System integration
FieldGate SWG50
34
Hauser
HART command Type
Memory address
Device variable
Register count
105
Read
40361
Burst mode control code
22
40362
Command number expansion flag
40363
Device variable code assigned to slot 0
40364
Device variable code assigned to slot 1
40365
Device variable code assigned to slot 2
40366
Device variable code assigned to slot 3
40367
Device variable code assigned to slot 4
40368
Device variable code assigned to slot 5
40369
Device variable code assigned to slot 6
40370
Device variable code assigned to slot 7
40371
Burst message
40372
Maximum number of burst messages
supported by the device
40373 (2 bytes)
Extended command number
40374 - 40375
Update time in 1/32 of a millisecond
40376 - 40377
Maximum update time in 1/32 of a
millisecond
40378
Burst trigger mode code
40379
Device variable classification for trigger
value
40380
Units code
40381 - 40382
Trigger value
8.1.3
Modbus exception codes
Code
Meaning
0x01
No request bytes present (expanded mapping only).
Invalid read request for "Number of neighbors" register from sub-device (condensed mapping only).
0x02
Starting address does not exist in mapping.
0x03
Starting register valid, but length of requests spans at least one unmapped register
WirelessHART device disconnected (condensed mapping only).
0x06
WirelessHART field device is engaged in processing another command. Retry later.
0x0b
Indicates that no response was obtained from the target device.