Prosonic M
4 Function group "safety settings" (01)
Hauser
23
4.2
Function "output on alarm" (011), HART only
The current (in mA) which will be output in case of an alarm. This function is active when
you selected "
user specific
" in the "
output on alarm
"
(010)
function.
Caution!
This function is available for HART devices only!
4.3
Function "outp. echo loss" (012)
Use this function to set the output response on echo loss.
Selection:
•
alarm
•
hold
•
ramp %/min
alarm
On echo loss, the instrument switches to alarm state after an adjustable
"
delay time
"
(014)
. The output response depends on the configuration set in
"
output on alarm
"
(010)
.
ß
Þ
Þ