15 Trouble shooting
Prosonic M
72
EHauser
15
Trouble shooting
15.1 System error messages
Current error
Errors which the Prosonic M detects during commissioning or operation are displayed:
•
In the
"measured value" (000)
function
•
In the
"diagnostics" (0A)
function group in the
"present error" (0A0) function
(only the highest priority error is displayed; in the case of multiple errors, you can scroll
between the different error messages by pressing
+
or
-
.)
Last error
The last error is displayed in the
"diagnostics" (0A)
function group in the
"previous
error" (0A1)
function. This display can be deleted in the
"clear last error" (0A2)
function.
Types of errors
Type of error
Symbol
Meaning
Alarm (A)
Continuo
us
The output signal assumes a value which can be set using the
"
output on
alarm
" (010)
function:
• MAX: 110 %, 22mA
• MIN: -10%, 3.8 mA
• Hold: last value is on hold
• User-specific value
Warning (W)
Flashing
The device continues measurement. An error message is displayed.
Alarm/Warning
(E)
You can define whether the error should behave as an alarm or as a warning.