Technical data
Proline Promag 51
84
Hauser
10.1.7
Operating conditions: other operating conditions
Measured variable
Volume
Fluid conductivity
Cold water with a minimum conductivity of 5
μ
S/cm.
(with demineralized water 20
μ
S/cm)
Note that in the case of the remote version, the requisite conductivity is influenced by the length of
the connecting cable
Inlet run
At least 5 × DN straight pipe section upstream from the measuring equipment
Outlet run
At least 2 × DN straight pipe section upstream from the measuring equipment
Rectifier
Not required
Storage temperature
The storage temperature corresponds to the operating temperature range of the measuring
transmitter and the appropriate measuring sensors.
"
Caution!
• The measuring device must be protected against direct sunlight during storage in order to avoid
unacceptably high surface temperatures.
• Choose a storage location where moisture does not collect in the measuring device. This will help
prevent fungus or bacteria infestation which can damage the liner.
Degree of protection
• Standard: IP 67 (NEMA 4X) for transmitter and sensor
• Optional: IP 68 (NEMA 6P) for remote version of Promag W and P sensor
Shock and vibration resistance
Acceleration up to 2 g by analogy with IEC 60068-2-6
(high-temperature version: no data available)
Electromagnetic compatibility
(EMC)
• To IEC/EN 61326 and NAMUR recommendation NE 21.
• Emission: As per industry limit values, EN 55011