Use in protective systems
Proline Promass 500
20
Hauser
For alarm monitoring, the downstream automation system must be able to recognize both
maximum alarms (≥ 21 mA) and minimum alarms (≤ 3.6 mA).
6.1.5
Alarm and warning messages
Additional information is provided by the alarm and warning messages output in the form of
diagnostic events and associated event texts.
NOTICE
A diagnostic message is displayed even though the diagnostic event is no longer active in
the unlocked SIL mode.
When SIL mode is activated, additional diagnostics are activated. If a diagnostic event is
pending and the locked SIL mode is deactivated, the diagnostic message remains as long as
the error is still present.
‣
In this case, the device must be disconnected briefly from the power supply .
‣
When the device is then restarted, a self-check is carried out, and the diagnostics event is
reset where applicable.
This behavior occurs in the case of the following diagnostic messages:
803 Current loop
diagnostic message
6.2
Parameter configuration for safety-related applications
6.2.1
Calibration of the measuring point
The measuring point is calibrated via the operating interfaces. A wizard guides you
systematically through all the submenus and parameters that have to be set for configuring
the measuring device.
For detailed information on the operating options, see the Operating
Instructions.→ 11
For detailed information on configuring the measuring device, see the Operating
Instructions and Description of Device Parameters → 11
To activate the SIL mode, the device must run through a confirmation sequence. While
running through this sequence, critical parameters are either set automatically by the device
to standard values or transferred to the local display/operating tool to enable verification of
the setting. On completion of parameter configuration, the SIL mode of the device must be
enabled with a SIL locking code.