Proline Promass 500
Use in protective systems
Hauser
23
NOTICE
If these preconditions are not met, the message "SIL preparation = failed" appears on the
display along with the parameter that failed to meet the preconditions under 1.
The SIL confirmation sequence is not continued.
‣
Check preconditions.
If the preconditions are met, the message
SIL preparation = finished
appears on the display.
Once the preconditions have been met, the device automatically switches the following
parameters to safety-oriented settings:
Setup
Current output 1
Partial filled
pipe detection
Measuring mode
(4 mA value)
=
Forward flow
Response time
part. filled p. d.
=
0
A0015326-EN
Simulation
Assign simulat.
process variable
Simulation
current output 1
=
Off
Diagnostics
=
Off
A0015327-EN
The diagnostic behavior is set in such a way that the measuring device is set to the safe state
when an error occurs. This means that the diagnostic messages listed in the graphic are set to
alarm and the current output adopts the configured failsafe mode → 19.