Use in protective systems
Proline Promass 500
36
Hauser
3. Document results of proof test in accordance with the safety management guidelines
applicable to the system.
NOTICE
With the test sequences described, at least 49 % of the undetected dangerous failures
can be detected. The influence of systematic errors on the safety function is not fully
covered by the test. Systematic errors can be caused, for example, by medium properties,
operating conditions, build-up or corrosion.
‣
If one of the test criteria from the test sequences described above is not fulfilled, the device
may no longer be used as part of a protective system.
‣
Take measures to reduce systematic errors.
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Current output
1 to n simulation
–
Switch the simulation of
the current output on and
off.
On
Off
Value current
output 1 to n
In the
Current output
1 to n simulation
parameter, the
On
option
is selected.
Enter the current value for
simulation.
• 1. Default
value: Select
4.0 mA.
• 2. Default
value: Select
20.0 mA.
3.59 to 22.5 mA
3.59 mA