Levelflex M FMP43 with PROFIBUS PA
Operation
Hauser
53
Data strings
In der Slot/Index table some data types, e.g. DS-33 are marked by an asterisk. These are data strings
according to the PROFIBUS-PA specifications part 1, Version 3.0. They contain several elements,
which are addressed by an additional subindex. The following table gives an example.
5.5.7
Scaling of the output data
The on-site display and the digital output are working independently of each other.
On-site display
The on-site display always displayes the main value V0H0 directly from the Transducer Block.
Digital output
For the digital output this value is rescaled in two steps:
L00-FMUx3xxx-05-00-00-en-001
1.
In a first step, the main value is mapped to the interval [0;1]. PV_SCALE_MIN and
PV_SCALE_MAX determine the limits of this mapping.
Measured level
V9H6
1
234
4
FLOAT
x
dynamic
Gap
1
235
Application parameter
V9H8
1
236
1
UNSIGNED8
x
dynamic
Gap
1
237
Tag no.
VAH0
1
238
STRING
x
const
Profile revision
VAH1
1
239
STRING
x
x
static
Version string
VAH2
1
240
STRING
x
const
Gap
1
241
Serial no.
VAH4
1
242
STRING
x
x
static
Distance unit
VAH5
1
243
2
UNSIGNED16
x
x
static
Gap
1
244 -
245
Download mode
VAH8
1
246
1
UNSIGNED8
x
x
static
Data type
Subindex
Typ
Size [bytes]
DS-33
1
FLOAT
4
5
UNSIGNED8
1
Parameter
E+H Matrix
(CW II)
Slot
Index
Size
[bytes]
Type
Read
Write
Storage
Class
0
1
0
1
PV_SCALE_MAX
PV_SCALE_MIN
OUT_SCALE
MIN
OUT_SCALE
MAX
V0H0
AI_OUT
(V6H2)
PLC
from Transducer
block
Summary of Contents for Levelflex M FMP43
Page 4: ...Brief overview Levelflex M FMP43 with PROFIBUS PA 4 Endress Hauser...
Page 104: ...Appendix Levelflex M FMP43 with PROFIBUS PA 104 Endress Hauser...
Page 106: ...Levelflex M FMP43 with PROFIBUS PA Index 106 Endress Hauser...
Page 108: ...www endress com worldwide BA358F 00 en 07 07 No 71041163 CCS FM SGML 6 0 ProMoDo 71041163...