Operation options
Liquipoint FTW33
18
Hauser
7
Operation options
7.1
Local operation
7.1.1
Operational display (LEDs)
4
3
1
2
2
1
3
4
A0038425
6
LEDs in the housing cover
1
Status/Communication
2
Switch status/switch output 2
3
Warning/Maintenance required
4
Switch status/switch output 1
There is no external signaling via LEDs on the metal housing cover (IP69). A
connecting cable with an M12 plug and LED indicator can be ordered as an accessory
if necessary. See "Accessories".
7.2
Operation via test magnet
The test magnet is included in the scope of delivery.
A switch output function test can be carried out directly at the machine by means of a test
magnet.
7.3
Operation via IO-Link operating menu
7.3.1
IO-Link information
IO-Link is a point-to-point connection for communication between the device and an IO-
Link master. This requires an IO-Link compatible module (IO-Link master) for operation.
The IO-Link communication interface enables direct access to the process and diagnostic
data. It also provides the option of configuring the device while in operation.
Physical layer, the devices supports the following features:
• IO-Link specification: version 1.1
• IO-Link Smart Sensor Profile 2nd Edition
• SIO mode: Yes
• Speed: COM2; 38.4 kBaud
• Minimum cycle time: TBD
• Process data width: 16 bit
• IO-Link data storage: Yes
• Block configuration: Yes
• Device operational: The device is operational 4 s after the supply voltage has been
applied