Diagnostics and troubleshooting
Micropilot FMR56, FMR57 FOUNDATION Fieldbus
102
Hauser
Diagnostic
number
Short text
Remedy instructions
Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
485
Simulation measured
value
Deactivate simulation
C
Warning
494
Switch output
simulation
Deactivate simulation switch
output
C
Warning
495
Simulation diagnostic
event
Deactivate simulation
C
Warning
497
Simulation block output Deactivate simulation
C
Warning
585
Simulation distance
Deactivate simulation
C
Warning
586
Record map
Recording of mapping
please wait
C
Warning
Diagnostic of process
801
Energy too low
Increase supply voltage
S
Warning
825
Operating temperature 1. Check ambient temperature
2. Check process temperature
F
Alarm
921
Change of reference
1. Check reference configuration
2. Check pressure
3. Check sensor
S
Warning
941
Echo lost
Check parameter 'DC value'
F
Alarm
942
In safety distance
1. Check level
2. Check safety distance
3. Reset self holding
S
Alarm
943
In blocking distance
Reduced accuracy
Check level
S
Warning
950
Advanced diagnostic 1
to 2 occured
Maintain your diagnostic event
M
Warning
1)
Diagnostic behavior can be changed.
13.7 Event logbook
13.7.1 Event history
A chronological overview of the event messages that have occurred is provided in the
Event list
submenu
.
Navigation path
Diagnostics → Event logbook → Event list
A maximum of 100 event messages can be displayed in chronological order.
The event history includes entries for:
• Diagnostic events
• Information events
4)
This submenu is only available for operation via local display. In the case of operation via FieldCare, the event list can be displayed with the "Event
List / HistoROM" functionality of FieldCare.