Operating menu
Micropilot FMR56, FMR57 FOUNDATION Fieldbus
128
Hauser
Selection
• Very slow < 0,5m (1,6ft) /h
• Slow < 1m (3,3ft) /h
• Standard < 2m (6,5ft) /h
• Medium < 4m (13ft) /h
• Fast < 8m (26ft) /h
• Very fast > 8m (26ft) /h
• No filter / test
Factory setting
Standard < 2m (6,5ft) /h
Additional information
It is strongly recommended to adjust this parameter to the actual maximum filling speed of
the process.
Max. draining speed solid
Navigation
Setup → Max.drain solid
Prerequisite
Solid
Description
Select expected maximum draining speed.
Selection
• Very slow < 0,5m (1,6ft) /h
• Slow < 1m (3,3ft) /h
• Standard < 2m (6,5ft) /h
• Medium < 4m (13ft) /h
• Fast < 8m (26ft) /h
• Very fast > 8m (26ft) /h
• No filter / test
Factory setting
Standard < 2m (6,5ft) /h
Additional information
It is strongly recommended to adjust this parameter to the actual maximum draining speed
of the process.
Empty calibration
Navigation
Setup → Empty calibr.
Description
Specify the distance E between the process connection and the minimum level (0%). This
defines the starting point of the measuring range.
User entry
Depending on the antenna
Factory setting
Depending on the antenna