Micropilot FMR56, FMR57 FOUNDATION Fieldbus
Operating menu
Hauser
149
Maximum value
Navigation
Setup → Advanced setup → Linearization → Maximum value
Prerequisite
Linearization type (→ 146)
has one of the following values:
• Linear
• Pyramid bottom
• Conical bottom
• Angled bottom
• Horizontal cylinder
• Sphere
Description
Specify the maximum content of the vessel (100%) measured in the units after
linearization.
User entry
–50
000.0 to 50
000.0 %
Factory setting
100.0 %
Diameter
Navigation
Setup → Advanced setup → Linearization → Diameter
Prerequisite
Linearization type (→ 146)
has one of the following values:
• Horizontal cylinder
• Sphere
Description
Specify tank diameter.
User entry
0 to 9
999.999 m
Factory setting
2 m
Additional information
The unit is defined in the
Distance unit
Intermediate height
Navigation
Setup → Advanced setup → Linearization → Intermed. height
Prerequisite
Linearization type (→ 146)
has one of the following values:
• Pyramid bottom
• Conical bottom
• Angled bottom
Description
Specify intermediate height H.
User entry
0 to 200 m
Factory setting
0 m
Summary of Contents for Micropilot FMR56
Page 197: ......
Page 198: ...www addresses endress com 71344036 71344036 ...