Micropilot FMR56, FMR57 FOUNDATION Fieldbus
Operating menu
Hauser
151
Conditions the linearization table must meet:
• The table may consist of up to 32 pairs of values "Level - Linearized Value".
• The table must be monotonic (monotonically increasing or decreasing).
• The first linearization point must refer to the minimum level.
• The last linearization point must refer to the maximum level.
Before entering a linearization table, the values for
and
Full calibration (→ 129)
must be set correctly.
If values of the table need to be changed after the full or empty calibration have been
changed, a correct evaluation is only ensured if the existing table is deleted and the
complete table is entered again. To do so delete the existing table (
Table mode
=
Clear table
). Then enter a new table.
How to enter the table
• Via FieldCare
The table points can be entered via the
Table number (→ 151)
Level (→ 151)
and
parameters. As an alternative, the graphic table editor
may be used: Device Operation → Device Functions → Additional Functions →
Linearization (Online/Offline)
• Via local display
Select the
Edit table
submenu to call up the graphic table editor. The table is displayed
and can be edited line by line.
The factory setting for the level unit is "%". If you want to enter the linearization table
in physical units, you must select the appropriate unit in the
Level unit
parameter
Table number
Navigation
Setup → Advanced setup → Linearization → Table number
Prerequisite
Linearization type (→ 146)
=
Table
Description
Select table point you are going to enter or change.
User entry
1 to 32
Factory setting
1
Level (Manual)
Navigation
Setup → Advanced setup → Linearization → Level
Prerequisite
•
=
Table
•
Table mode (→ 150)
=
Manual
Description
Enter level value of the table point (value before linearization).
User entry
Signed floating-point number
Summary of Contents for Micropilot FMR56