Micropilot FMR56, FMR57 FOUNDATION Fieldbus
Operating menu
Hauser
155
level change during operation. Signals which are already in the blocking distance when the
device is switched on, are ignored.
This behavior is only valid if the following two conditions are met:
• Expert → Sensor → Echo tracking → Evaluation mode =
Short time history
or
Long
time history
)
• Expert → Sensor → Gas phase comp. → GPC mode=
On
,
Without correction
or
External correction
If one of these conditions is not met, signals in the blocking distance will always be
ignored.
If required, a different behavior for signals in the blocking distance can be defined by
the Hauser service.
BD
A0023041
38
Blocking distance (BD) for bulk solid measurements