Operating menu
Micropilot FMR56, FMR57 FOUNDATION Fieldbus
160
Hauser
Switch-off delay
Navigation
Setup → Advanced setup → Switch output → Switch-off delay
Prerequisite
•
Switch output function (→ 156)
Limit
•
Off
Description
Define switch-off delay.
User entry
0.0 to 100.0 s
Factory setting
0.0 s
Failure mode
Navigation
Setup → Advanced setup → Switch output → Failure mode
Description
Define output behavior in alarm condition.
Selection
• Actual status
• Open
• Closed
Factory setting
Open
Switch status
Navigation
Setup → Advanced setup → Switch output → Switch status
Description
Displays the current state of the switch output.
Invert output signal
Navigation
Setup → Advanced setup → Switch output → Invert outp.sig.
Description
Specify whether the output signal is to be inverted.
Selection
• No
• Yes
Factory setting
No
Summary of Contents for Micropilot FMR56