Commissioning via operating menu
Micropilot FMR56, FMR57 FOUNDATION Fieldbus
76
Hauser
11. When operating via local display:
Navigate to: Setup → Mapping → Confirm distance
Compare distance indicated on the display to real distance in order to start the
recording of an interference echo map.
12. When operating via operating tool:
Navigate to: Setup → Confirm distance
Compare distance indicated on the display to real distance in order to start the
recording of an interference echo map.
13. Navigate to: Setup → Advanced setup → Level → Level unit
Select level unit: %, m, mm, ft, in (Factory setting: %)
It is strongly recommended to adjust the maximum filling and draining speed to the
actual process.