Commissioning (block-based operation)
Micropilot FMR56, FMR57 FOUNDATION Fieldbus
92
Hauser
25
Changed state of the "Fail Map" and "Check Map" columns
Make sure that for each group the corresponding bit is set to
1
in at least one of the
allocation parameters. Otherwise no event category is transmitted with the event
message. As a consequence the message will not be recognized by the control system.
The
Alarm detection enable
screen is used to configure the detection of diagnostic
events but not the transmission of event messages to the bus. The latter is configured
on the
Alarm broadcast enable
screen, which is operated exactly in the same way as
the
Alarm detection enable
screen. Status information is only transmitted to the bus
if the Resource Block is in the
Auto
mode.