Operating menu
Micropilot FMR56, FMR57 FOUNDATION Fieldbus
142
Hauser
Additional information
The value specified in this parameter is added to the measured level (before linearization).
Tank/silo height
Navigation
Setup → Advanced setup → Level → Tank/silo height
Description
Specify total height of the tank or silo as measured from the process connection.
User entry
–999.9999 to 999.9999 m
Factory setting
Empty calibration (→ 128)
Additional information
If the parametrized measuring range (
Empty calibration (→ 128)
) differs significantly
from the tank or silo height, it is recommended to enter the tank or silo height. Example:
Continuous level monitoring in the upper third of a tank or silo.
E
1
0%
A0019868
35
'"Tank/silo height" parameter (→ 142)' for measurements in bulk solids
E
1
Tank/silo height (→ 142)
For tanks with conical outlet,
Tank/silo height
should not be changed as in this type
of applications
is usually
not
<< the tank or silo
height.
Summary of Contents for Micropilot FMR56
Page 197: ......
Page 198: ...www addresses endress com 71344036 71344036 ...