Operating menu
Micropilot FMR56, FMR57 FOUNDATION Fieldbus
186
Hauser
17.4.7 "Simulation" submenu
The
Simulation
submenu is used to simulate specific measuring values or other
conditions. This helps to check the correct configuration of the device and connected
control units.
Conditions which can be simulated
Condition to be simulated
Associated parameters
Specific value of a process variable
• Assign measurement variable (→ 189)
• Value process variable (→ 189)
Specific state of the switch output
• Switch output simulation (→ 189)
• Switch status (→ 190)
Existence of an alarm
Simulation device alarm (→ 190)
Enable/disable simulation
The simulation of measured values can be enabled or disabled via a hardware switch (SIM
switch) at the electronics. Simulating a measured value is only possible if the SIM switch is
in the ON position.
The switch output can always be simulated, irrespective of the position of the SIM switch.
+
E
–
3 mm
XXXXXXXXXXXXX
WP
CDI
SIM
ON
OFF
A0025882
1. Loosen the securing clamp.
2. Unscrew the housing cover.
Summary of Contents for Micropilot FMR56
Page 197: ......
Page 198: ...www addresses endress com 71344036 71344036 ...