Integration into a FOUNDATION Fieldbus network
Micropilot FMR56, FMR57 FOUNDATION Fieldbus
70
Hauser
9.6.6
Expert Information Transducer Block
The parameters of the
Expert Information Transducer Block
are described in
GP01017F: "Micropilot FMR5x - Description of Device Parameters - FOUNDATION
Fieldbus"
Name
Label
Index Data type
Size (Bytes) Storage Class Write access MODE_BLK
abs_echo_ampl
Absolute echo amplitude
15
Standard
5
rel_echo_ampl
Relative echo amplitude
16
Standard
5
Dynamic
rel_eop_ampl
Tank bottom echo amplitude
17
Standard
5
Dynamic
noise_signal_val
Noise of signal
18
FLOAT
4
Dynamic
electronic_temperature
Electronic temperature
19
Standard
5
Dynamic
found_echoes
Found echoes
20
ENUM16
2
Dynamic
temperature_unit
Temperature unit
21
ENUM16
2
Static
Maintenance OOS
max_electr_temp
Max. electronic temperature
22
FLOAT
4
Static
Development AUTO
application_parameter
Application parameter
23
ENUM16
2
Dynamic
time_max_electr_temp
Time max. electronics temperature 24
STRING
14
Dynamic
measurement_frequency
Measurement frequency
25
FLOAT
4
Dynamic
min_electr_temp
Min. electronics temperature
26
FLOAT
4
Static
Development AUTO
time_min_electr_temp
Time min. electronics temperaturer 27
STRING
14
Dynamic
reset_min_max_temp
Reset min/max. Temp.
28
ENUM16
2
Static
Service
AUTO
used_calculation
Used calculation
29
ENUM16
2
Dynamic
tank_trace_state
Status Tanktrace
30
ENUM16
2
Dynamic
max_draining_speed
Max. draining speed
31
FLOAT
4
Static
Development AUTO
max_filling_speed
Max. filling speed
32
FLOAT
4
Static
Entwicklung AUTO
time_max_level
Time max. level
33
STRING
14
Dynamic
max_level_value
Max. level value
34
FLOAT
4
Static
Development AUTO
time_min_level
Time min. level
35
STRING
14
Dynamic
min_level_value
Min. level
36
FLOAT
4
Static
Development AUTO
reset_min_max
Reset min./max.
37
ENUM16
2
Static
Service
AUTO
appl_param_changed_flags Application parameter
38
UINT16
2
Static
Production
AUTO
terminal_voltage_ds
Terminal voltage
39
Standard
5
Dynamic
area_of_incoupling
Area of incoupling
40
Standard
5
Dynamic
linearization_type_ro
Linearization type
41
ENUM16
2
Static
Maintenance OOS
operating_mode
Operating mode
42
ENUM16
2
Static
Maintenance OOS
decimal_places_menu_ro
Decimal places menu
43
ENUM16
2
Static
Maintenance AUTO
activat_sw_option
Activate SW option
44
UINT32
4
Static
Maintenance AUTO
sw_option_active_overview Sw option active overview
45
BIT_ENUM32 4
Dynamic
debug_status
107
UINT8
1
Dynamic
x
AUTO
9.6.7
Service Sensor Transducer Block
The parameters of the
Service Sensor
Transducer Block can only be operated by
authorized Hauser service personnel.
Summary of Contents for Micropilot FMR56