Micropilot FMR56, FMR57 FOUNDATION Fieldbus
Commissioning (block-based operation)
Hauser
93
12.8.3 Configurable area
An event category can be individually defined for the following parameters - irrespective of
the group of events they belong to by default.
•
F941
: Echo lost
•
S942:
In safety distance
•
M950:
Advanced Diagnostic occurred
Prior to changing the event category, the event must be allocated to one of the bits 1 to 15.
This is performed by the parameters
FF912 ConfigArea_1
to
FF912ConfigArea_15
in
the
DIAGNOSTIC (TRDDIAG)
block. Thereafter, the selected bit can be switched from
0
to
1
in the desired allocation parameter.
Example
To change the category of error
942 "In safety distance"
from
Out of specification (S)
(default), to
Function check (C)
, proceed as follows.
1.
Use the FieldCare navigation window to navigate to the the following screen:
Expert
→ Communication → Field diagnostics → Alarm detection enable
.
2.
By default all
Configurable Area Bits
are set to
not used
.
3.
Select one of these bits (in the example: Configurable Area Bit 1) and select
In safety
distance
from the associated drop-down menu. Confirm the selection by pressing the
Enter key.
Summary of Contents for Micropilot FMR56
Page 197: ......
Page 198: ...www addresses endress com 71344036 71344036 ...