Appendix
Micropilot M FMR231 with FOUNDATION Fieldbus
100
Hauser
11.4
Sensor block
The Sensor block contains the parameters required to calibrate the device. These parameters can
also be addressed by using the VU331 display module. The calibration of the device is described in
Chapter 6.
11.4.1
Operation
Parameter changes from the tool are made off-line while the device is operating. The changes are
downloaded by first setting MODE_BLK = OOS then pressing the WRITE CHANGES button. Press
the READ ALL button to check the values stored in the device. Normally operation is resumed as
soon as MODE-BLK is set to AUTO.
11.4.2
Block administration parameters
11.4.3
Output values
11.4.4
Configuration parameters
The Sensor block also contains the configuration parameters, which are used to commission and
calibrate the instrument. They are identical to the functions of the operating menu, except for the
service parameters which are not accessible on the bus. Thus, the calibration procedure via the
display module (Chapter 6.4) is equally valid for a calibration via a network configuration tool.
A complete list of the configuration parameters can be found in the "Description of Instrument
Functions", BA221F/00/en.
Parameter
Description
MODE_BLK
See description in Resource block. The possible operating modes of the Sensor block are:
– AUTO: the block is operating as normal
– OOS: the block is out of service.
TAG_DESC
User description of the intended application of the block.
BLOCK_ERROR
Shows error status of software and hardware components
– Out-of-Service: the block is in OOS mode
Parameter
Description
PRIMARY_VALUE
Main value (level or volume).
SECONDARY_VALUE
Measured distance.
Summary of Contents for Micropilot M FMR231
Page 95: ...Micropilot M FMR231 with FOUNDATION Fieldbus Technical data Endress Hauser 95 ...
Page 112: ...Micropilot M FMR231 with FOUNDATION Fieldbus Index 112 Endress Hauser ...
Page 113: ......
Page 114: ...www endress com worldwide BA229F 00 ae 06 07 52009950 CCS FM SGML 6 0 ProMoDo 52008600 ...