Commissioning
Micropilot M FMR 240 with Foundation Fieldbus
62
E Hauser
6.4
Basic Setup with the VU 331
Function "measured value" (000)
This function displays the current measured value in the selected unit
(see "
customer unit
"
(042)
function). The number of digits after decimal point can be selected in
the "
no.of decimals
"
(095)
function.
"
Caution!
When using FMR 240 with
Wave Guide antenna
"
stilling well
" must be selected in the "
tank
shape
"
(002)
funktion.
The instrument is calibrated on delivering. The following parameters are default:
• "
tank shape
"
(002)
- "
stilling well
",
please don’t change!
• "
pipe diameter
"
(007)
- ~21 mm,
please don’t change!
• "
empty calibr.
"
(005)
- zero point=pipe end,
possible readjust!
• "
full calibr.
"
(006)
- span=reference point (
→
Page 60),
possible readjust!
6.4.1
Function group "basic setup" (00)
Function "tank shape" (002)
This function is used to select the tank shape.
Selection:
•
dome ceiling
• horizontal cyl
• bypass
• stilling well,
also for Wave Guide antenna use.
• flat ceiling
• sphere
⇒