Micropilot M FMR 240 with Foundation Fieldbus
Commissioning
E Hauser
77
!
Note!
You can also specify the pipe diameter in this display.
If "
flat ceiling
" is selected in the "
tank shape
" function, the following display appears on the
screen:
• empty calibr. (for a description, see Page 65)
• full calibr.(for a description, see Page 66)
L00-FMR2xxxx-20-00--00-en-006
Basic Setup step 4/4:
• This step starts the tank mapping
• The measured distance and the current measured value are always displayed in the header
• A description is given on Page 68
L00-FMR2xxxx-20-00--00-en-007