Commissioning
Proline 200 HART
38
Hauser
Parameter overview with brief description
Parameter
Description
User entry
Factory setting
Device tag
Enter the name for the
measuring point.
Max. 32 characters, such as
letters, numbers or special
characters (e.g. @, %, /).
Prowirl
8.6
Protecting settings from unauthorized access
The following write protection options exist in order to protect the configuration of the
measuring device from unintentional modification:
• Protect access to parameters via access code
• Protect access to local operation via key locking
• Protect access to measuring device via write protection switch
For detailed information on protecting the settings against unauthorized access, see the
Operating Instructions for the device.
8.7
Application-specific commissioning
8.7.1
Steam application
Select medium
Navigation:
Setup → Medium selection
1. Call up the
Medium selection
wizard.
2. In the
Select medium
parameter, select the
Steam
option.
3. When pressure measured value is read in
1)
:
In the
Steam calculation mode
parameter, select the
Automatic (p-/T-compensated)
option.
4. If pressure measured value is not read in:
In the
Steam calculation mode
parameter, select the
Saturated steam (T-
compensated)
option.
5. In the
Steam quality value
parameter, enter the steam quality present in the pipe.
Without Wet Steam Detection/Measurement application package: Measuring
device uses this value to calculate the mass flow of the steam.
With Wet Steam Detection/Measurement application package: Measuring device
uses this value if the steam quality cannot be calculated (steam quality is not
compliant with basic conditions).
1)
Sensor version option "mass (integrated pressure and temperature measurement)", Pressure read in via current
input/HART/