Proline Cubemass C 500
46
Hauser
Relay output
Standard installation cable is sufficient.
Current input 0/4 to 20 mA
Standard installation cable is sufficient.
Status input
Standard installation cable is sufficient.
Choice of connecting cable between the transmitter and sensor
Depends on the type of transmitter and the installation zones
2
3
C
1
3
B
1
3
A
1
3
A
1
3
B
2
3
C
4
5
6
A0032476
1
Proline 500 digital transmitter
2
Proline 500 transmitter
3
Sensor Cubemass
4
Non-hazardous area
5
Hazardous area: Zone 2; Class I, Division 2
6
Hazardous area: Zone 1; Class I, Division 1
A
Standard cable to 500 digital transmitter → 46
Transmitter installed in the non-hazardous area or hazardous area: Zone 2; Class I, Division 2 / sensor
installed in the hazardous area: Zone 2; Class I, Division 2
B
Standard cable to 500 digital transmitter → 47
Transmitter installed in the hazardous area: Zone 2; Class I, Division 2 / sensor installed in the hazardous
area: Zone 1; Class I, Division 1
C
Signal cable to 500 transmitter → 49
Transmitter and sensor installed in the hazardous area: Zone 2; Class I, Division 2 oder Zone 1;
Class I, Division 1
A: Connecting cable between sensor and transmitter: Proline 500 – digital
Standard cable
A standard cable with the following specifications can be used as the connecting cable.
Design
4 cores (2 pairs); uninsulated stranded CU wires; pair-stranded with common
shield
Shielding
Tin-plated copper-braid, optical cover ≥ 85 %
Loop resistance
Power supply line (+, –): maximum 10 Ω
Cable length
Maximum 300 m (1
000 ft), see the following table.