6 Commissioning
Proline Promass 83 FOUNDATION Fieldbus
60
Hauser
6.3.2
Quick Setup “Gas Measurement”
Promass 83 is not only suitable for measuring liquid flow. Direct mass measurement based on the
Coriolis principle is also possible for measuring the flow rate of gases. To do so, the corresponding
device functions can be configured via the configuration program (e.g. Commuwin II) or via the
local display.
!
Note!
• Before carrying out the Quick Setup “Gas Measurement” the Quick Setup “Commissioning”
(see Page 58) has to be executed.
• Only mass and corrected volume flow can be measured and output with the gas measurement
mode. Note that direct density and/or volume measurement is not possible!
• The flow ranges and measuring accuracy that apply to gas measurement are not the same as those
for liquids.
Gas measurement commissioning (with local display
k
)
This “Gas Measurement” Quick Setup menu guides the user systematically through all the device
functions that have to be configured for measuring operations with gas.
The “Gas measurement” Quick Setup menu can be called up in the function matrix via two separate
functions :
• via the QS GAS MEASUREMENT (1004) function
• via the QS COMMISSIONING (1002) function
F06-83PBxxxx-19-xx-xx-en-001
Fig. 32:
Quick Setup for measuring operation with gases. Recommended settings
→
see next page
+
+
E
-
+
HAUSER
E
ESC
1004
B
6400
6402
6403
E
Setup
Gas measurement
Quick
Setup
Assign
Low flow cut off
On value
Low flow cut off
Off value
Low flow cut off
HOME
POSITION
Summary of Contents for Proline Promass 83
Page 24: ...3 Installation Proline Promass 83 FOUNDATION Fieldbus 24 Endress Hauser ...
Page 34: ...4 Wiring Proline Promass 83 FOUNDATION Fieldbus 34 Endress Hauser ...
Page 64: ...6 Commissioning Proline Promass 83 FOUNDATION Fieldbus 64 Endress Hauser ...
Page 66: ...7 Maintenance Proline Promass 83 FOUNDATION Fieldbus 66 Endress Hauser ...
Page 90: ...9 Trouble shooting Proline Promass 83 FOUNDATION Fieldbus 90 Endress Hauser ...
Page 116: ...Index Proline Promass 83 FOUNDATION Fieldbus 116 Endress Hauser ...