Proline Promass 83 FOUNDATION Fieldbus
9 Trouble-shooting
Hauser
75
121
Device status message (FF):
Compatibility AMP-I/O Modul
– Err. No. 121
Local display:
S
CHECKSUM TOTAL.
!
# 121
[.....] Quality = BAD
OUT. QUALITY = BAD
Cause:
Due to different software versions, I/O
board and amplifier board are only par-
tially compatible (possibly restricted
functionality).
!
Note!
– This message is only listed in the
error history.
– Nothing is displayed on the display.
Remedy:
Module with lower software version
has either to be actualizied by ToF-
Tool/Fieldtool package with the requi-
red software version or the module has
to be replaced.
Spare parts
[.....] Substatus = Device failure
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Device needs
maintenance now
BLOCK_ERR = Input Failure
(faulty input value from Transducer
Block)
Transducer_Error = Electronics
failure
205
Device status message (FF):
Save to T-DAT failed –
Err. No. 205
Local display:
S
LOAD T-DAT
!
# 205
[.....] Quality = BAD
OUT. QUALITY = BAD
Cause:
Data backup (download) to T-DAT fai-
led or error when accessing the values
stored in the T-DAT (upload).
Remedy:
1.
Check whether the
T-DAT is correctly plugged into the
amplifier board
2.
Replace T-DAT if faulty.
Spare parts
→
Check the spare part set number to
ensure that the new, replacement
DAT is compatible with the measu-
ring electronics.
3.
Replace measuring electronics
boards if necessary.
Spare parts
[.....] Substatus = Device failure
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Device needs
maintenance now
BLOCK_ERR = Input Failure
(faulty input value from Transducer
Block)
Transducer_Error = Electronics
failure
206
Device status message (FF):
Restore from T-DAT failed –
Err. No. 206
Local display:
S
SAVE T-DAT
!
# 206
[.....] Quality = BAD
OUT. QUALITY = BAD
[.....] Substatus = Device failure
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Device needs
maintenance now
BLOCK_ERR = Input Failure
(faulty input value from Transducer
Block)
Transducer_Error = Electronics
failure
251
Device status message (FF):
Communication failure –
Err. No. 251
Local display:
S
COMMUNIC. AMP.
$
# 251
[.....] Quality = BAD
OUT. QUALITY = BAD
Cause:
Internal communication fault on the
amplifier board.
Remedy:
Remove the amplifier board.
Spare parts
[.....] Substatus = Device failure
OUT. SUBSTATUS = Device
Failure
BLOCK_ERR = Device needs
maintenance now
BLOCK_ERR = Input Failure
(faulty input value from Transducer
Block)
Transducer_Error = I/O failure
(input/output error)
No.
Device status message FF
(Diag. - Act. Syst. Cond.)
Message on local display
Transducer block
Error messages
[.....] = process variable (e.g. mass
flow, volume flow, ...)
Analog Input Funct. Block
Error messages
Cause/remedy
Summary of Contents for Proline Promass 83
Page 24: ...3 Installation Proline Promass 83 FOUNDATION Fieldbus 24 Endress Hauser ...
Page 34: ...4 Wiring Proline Promass 83 FOUNDATION Fieldbus 34 Endress Hauser ...
Page 64: ...6 Commissioning Proline Promass 83 FOUNDATION Fieldbus 64 Endress Hauser ...
Page 66: ...7 Maintenance Proline Promass 83 FOUNDATION Fieldbus 66 Endress Hauser ...
Page 90: ...9 Trouble shooting Proline Promass 83 FOUNDATION Fieldbus 90 Endress Hauser ...
Page 116: ...Index Proline Promass 83 FOUNDATION Fieldbus 116 Endress Hauser ...
Page 118: ...www endress com worldwide BA065D 06 en 12 04 50098623 FM SGML 6 0 ...