Proline Promass 83 FOUNDATION Fieldbus
9 Trouble-shooting
Hauser
77
383
Device status message (FF):
Carrier tube sensor defect – Err.
No. 383
Local display:
S
CARR.TEMP.MIN
$
# 383
[.....] Quality = BAD
OUT. QUALITY = BAD
Cause:
The temperature sensor on the carrier
tube is likely defective.
Remedy:
Check the following electrical
connections before you contact your
Hauser service organisation:
– Verify that the sensor signal cable
connector is correctly plugged into
the amplifier board
– Remote version:
Check sensor and transmitter termi-
nal connections No. 11 and No. 12
[.....] Substatus = Sensor failure
OUT. SUBSTATUS = Sensor
Failure
BLOCK_ERR = Device needs
maintenance now
BLOCK_ERR = Input Failure
(faulty input value from Transducer
Block)
Transducer_Error = Mechanical
failure
384
Device status message (FF):
Carrier tube sensor defect – Err.
No. 384
Local display:
S
CARR.TEMP.MAX
$
# 384
[.....] Quality = BAD
OUT. QUALITY = BAD
[.....] Substatus = Sensor failure
OUT. SUBSTATUS = Sensor
Failure
BLOCK_ERR = Device needs
maintenance now
BLOCK_ERR = Input Failure
(faulty input value from Transducer
Block)
Transducer_Error = Mechanical
failure
385
Device status message (FF):
Measuring exiter coil defect –
Err. No. 385
Local display:
S
INL.SENS.DEF.
$
# 385
[.....] Quality = BAD
OUT. QUALITY = BAD
Cause:
One of the measuring tube exciter coils
(inlet or outlet) is likely defective.
Remedy:
Check the following electrical
connections before you contact your
Hauser service organisation:
– Verify that the sensor signal cable
connector is correctly plugged into
the amplifier board
– Remote version:
Check sensor and transmitter termi-
nal connections No. 4, 5, 6 and 7
[.....] Substatus = Sensor failure
OUT. SUBSTATUS = Sensor
Failure
BLOCK_ERR = Device needs
maintenance now
BLOCK_ERR = Input Failure
(faulty input value from Transducer
Block)
Transducer_Error = Mechanical
failure
386
Device status message (FF):
Measuring exiter coil defect –
Err. No. 386
Local display:
S
OUTL.SENS.DEF.
$
# 386
[.....] Quality = BAD
OUT. QUALITY = BAD
[.....] Substatus = Sensor failure
OUT. SUBSTATUS = Sensor
Failure
BLOCK_ERR = Device needs
maintenance now
BLOCK_ERR = Input Failure
(faulty input value from Transducer
Block)
Transducer_Error = Mechanical
failure
387
Device status message (FF):
Measuring exiter coil defect –
Err. No. 387
Local display:
S
SEN.ASY.EXCEED
$
# 387
[.....] Quality = BAD
OUT. QUALITY = BAD
[.....] Substatus = Sensor failure
OUT. SUBSTATUS = Sensor
Failure
BLOCK_ERR = Device needs
maintenance now
BLOCK_ERR = Input Failure
(faulty input value from Transducer
Block)
Transducer_Error = Mechanical
failure
No.
Device status message FF
(Diag. - Act. Syst. Cond.)
Message on local display
Transducer block
Error messages
[.....] = process variable (e.g. mass
flow, volume flow, ...)
Analog Input Funct. Block
Error messages
Cause/remedy
Summary of Contents for Proline Promass 83
Page 24: ...3 Installation Proline Promass 83 FOUNDATION Fieldbus 24 Endress Hauser ...
Page 34: ...4 Wiring Proline Promass 83 FOUNDATION Fieldbus 34 Endress Hauser ...
Page 64: ...6 Commissioning Proline Promass 83 FOUNDATION Fieldbus 64 Endress Hauser ...
Page 66: ...7 Maintenance Proline Promass 83 FOUNDATION Fieldbus 66 Endress Hauser ...
Page 90: ...9 Trouble shooting Proline Promass 83 FOUNDATION Fieldbus 90 Endress Hauser ...
Page 116: ...Index Proline Promass 83 FOUNDATION Fieldbus 116 Endress Hauser ...
Page 118: ...www endress com worldwide BA065D 06 en 12 04 50098623 FM SGML 6 0 ...