6 Commissioning
Proline Promass 83 FOUNDATION Fieldbus
48
Hauser
12. Now configure all the device-specific parameters for flow measurement.
!
Note!
– Note that changes to the device parameters can only be made after entering a valid access
code in the parameter “Un-/Locking - Access Code”.
– The selection of the system units in the Transducer Block has no effect on the output value
OUT (AI Block). Units of the process variables which are transmitted via the FF-interface
must be specified separately in the Analog Input function block via the XD_SCALE and
OUT_SCALE parameter group.
13. Set the operating mode in the parameter group MODE_BLK (parameter TARGET) to AUTO.
Configuration of the “Analog Input Function Block”
The Promass 83 has seven Analog Input Function Blocks that can be assigned to the various process
variables (see below). The following description provides an example for Analog Input Function
Block No. 1.
14. Enter the desired name for the Analog Input Function Block.
Factory setting: ANALOG_INPUT_1_ xxxxxxxxxxx
15. Open the Analog Input Function Block.
16. Set the operating mode in the parameter group MODE_BLK (parameter TARGET) to OOS, i.e.
block Out Of Service.
17. Using the parameter CHANNEL select the process variable that is to be used as input variable
for the function block algorithm (scaling and limit value monitoring functions). The following
configurations are possible:
– CHANNEL = 1 (mass flow)
– CHANNEL = 2 (volume flow)
– CHANNEL = 3 (corrected volume flow)
– CHANNEL = 4 (density)
– CHANNEL = 5 (reference density)
– CHANNEL = 6 (temperature)
– CHANNEL = 7 (totalizer 1)
– CHANNEL = 8 (totalizer 2)
– CHANNEL = 9 (totalizer 3)
18. In parameter group XD_SCALE select the desired unit of measure and the block input range
(e.g. measurement range of the flow application) for the process variable in question.
"
Caution!
Make sure that the selected unit is suitable for the measurement variable of the selected pro-
cess variable. Otherwise the parameter BLOCK_ERROR will display the error message “Block
Configuration Error” and the block operating mode cannot be set to AUTO.
Summary of Contents for Proline Promass 83
Page 24: ...3 Installation Proline Promass 83 FOUNDATION Fieldbus 24 Endress Hauser ...
Page 34: ...4 Wiring Proline Promass 83 FOUNDATION Fieldbus 34 Endress Hauser ...
Page 64: ...6 Commissioning Proline Promass 83 FOUNDATION Fieldbus 64 Endress Hauser ...
Page 66: ...7 Maintenance Proline Promass 83 FOUNDATION Fieldbus 66 Endress Hauser ...
Page 90: ...9 Trouble shooting Proline Promass 83 FOUNDATION Fieldbus 90 Endress Hauser ...
Page 116: ...Index Proline Promass 83 FOUNDATION Fieldbus 116 Endress Hauser ...
Page 118: ...www endress com worldwide BA065D 06 en 12 04 50098623 FM SGML 6 0 ...