Commissioning
Prosonic M FMU44 HART
28
Hauser
A
B
C
D
E
F
G
A0038402
24
Some of the options in the "Process cond." function
A
Calm surface
B
Turb. surface
C
Add. agitator
D
Fast change
E
Standard solid
F
Solid dusty
G
Conveyor belt
-
Not in graphic: Standard liq. and Test: no filter
Description of options
•
Standard liq.
• For liquid applications that do not suit any of the options
• Average filter values and output damping
•
Calm surface
• For storage tanks with an immersion tube or bottom filling
• Large filtering range and output damping
→ Stable measured value, accurate measurement, slow response time
•
Turb. surface
• For storage and buffer tanks with turbulent surfaces due to free filling, mixing nozzles
or small bottom agitators
• Emphasis on filters to stabilize the input signal
→ Steady measured value, medium response time
•
Add. agitator
• For agitated surfaces due to agitators, e.g. vortex formation
• Large values are set for filters to stabilize the input signal
→ Steady measured value, medium response time
•
Fast change
• For fast changes in the level, particularly in small tanks
• Small values are set for the filters
→ Fast response time
→ Possibly unstable measured value
•
Standard solid
• For bulk solids applications that do not suit any of the options
• Average filter values and output damping