Prosonic M FMU44 HART
Diagnostics and troubleshooting
Hauser
35
W103 = Initializing
If the message does not disappear, replace the electronics
W153 = Initializing
• Wait a few seconds
• If the error remains active, switch the voltage off/on
W601 = Linearization curve not monotone
Correct the table, enter a table that increases monotonically
W611 = Less than 2 linearization points
Enter more value pairs
W621 = Simulation on
Switch off the simulation mode,
Output (06)
function group →
Simulation (065)
function
W681 = Current out of range
• Perform the basic setup
• Check linearization
W691 = Noise filling
10.5 Application errors
Error:
Measured value (000)
incorrect, measured
distance (008)
correct.
Example:
100%
F
0%
t →
A
B
D (008)
E
A0038459
A
Expected result
B
Error occurred
1. Check
Empty calibration (005)
and
Full calibration (006)
and correct.
2. Check the linearization and correct it:
Level/ullage (040)
,
Max. scale (046)
,
Diameter vessel (047)
, Linearization table.
Error:
Measured value (000)
and measured distance in
Distance (008)
incorrect.
Example: