Diagnostics and troubleshooting
Prosonic M FMU44 HART
36
Hauser
100%
F
0%
t →
A
B
D (008)
E
A0038459
A
Expected result
B
Error occurred
1. In the
Tank shape (002)
function, select the corresponding option for
measurements in a bypass or ultrasound guide pipe.
2. Perform mapping.
Error: No change of measured value when filling or emptying.
Example:
100%
0%
t →
A
B
A0038460
A
Expected result
B
Error occurred
1. Perform mapping.
2. Clean sensor.
3. Select a better installation position.
4. If very large interference echoes occur simultaneously, select "Off" in the
Detection
window (0A7)
function.
Error: If the surface is turbulent, the measured value jumps sporadically to higher levels.
Turbulent: e.g. when filling, emptying, or with running agitator
Examples:
100%
0%
A
B
t →
A0038461
A
Expected result
B
Error occurred