Teqwave H
Electrical connection
Hauser
29
7.4
Special connection instructions
7.4.1
Connection examples
Current output 4 to 20 mA
4...20 mA
2
1
3
A0028758
11
Connection example for current output, active, 4 to 20 mA
1
Automation system with current input (e.g. PLC)
2
Analog display unit: maximum load 500 Ω
3
Transmitter
Voltage output 0 to 10 V
2
1
3
0…10 V
A0035460
12
Connection example for voltage output, active, 0 to 10 V
1
Automation system with current or voltage input (e.g. PLC)
2
Analog display unit for voltage: the load must be at least 750 Ω
3
Transmitter
Switch output
1
2
3
A0035461
13
Connection example for switch output, passive
1
Automation system with switch input (e.g. PLC)
2
Supply voltage: max. AC 30 V/DC 50 V
3
Transmitter