101
.NoDataBurstConfigured
This bit indicates that the device concerned has not been configured with burst command 3,
9 or 33. The missing burst configuration is either discovered during the detailed
initialization procedure or following a change to the configuration. Command 3, 9 or 33
must be flagged in order to publish cyclic data via EtherNet/IP.
Burst configuration of the wired devices must be performed via the bridge device. Burst
commands that are sent directly to the wired device are not recognized and cause the
".NoDataBurstConfigured" bit to be flagged.
.NoCmd48BurstConfigured
This bit indicates that the device concerned has not been configured with burst command
48. The missing burst configuration is either discovered during the detailed initialization
procedure or following a change to the configuration. Command 48 must be flagged in order
to publish cyclic data via EtherNet/IP.
Burst configuration of the wired devices must be performed via the bridge device. Burst
commands that are sent directly to the wired device are not recognized and cause the
".NoCmd48BurstConfigured" bit to be flagged.
Note that the ".NoCmd48BurstConfigured" bit remains active for devices that do not support
Command 48, such as HART devices Revision 5.