Engineering
WirelessHART Fieldgate SWG70
64
E Hauser
10
Engineering
10.1
Instrument List
10.1.1 General
This leaf contains a list of instruments in the network. It is also possible to add individual
devices that are still to be connected.
1. Click on
Engineering => Instrument List
to open the dialog:
Instrument List
parameters
Parameter/Field
Meaning
Instrument List
Displays tabular information identifying the device:
• Long Tag: Long Tag of connected device
• IO card: Identifier of fieldgate card used by the device
• Channel: Identifier of card channel used by the device
• Device ID: HART serial number that is assigned at manufacturing time and that
differs for each HART device of a given type
• Extended Device Type Code: Unique code identifying the HART product family
Delete button
Deletes a device from the instrument list
– Press Apply to register the change in Fieldgate SWG70
– If the device is still communicating with the network, it will automatically
reappear in the list at the next refresh
– Caution! Deleting a device from the instrument list can change the Modbus
register address if the Modbus addresses have been automatically generated.
Export/Export CSV
Exports the current instrument list as a CSV file
Import/Import CSV
Imports an instrument list that has been stored as a CSV file
Import Project Tree (DTM)
In Offline Parameterize dialog, imports the network view to the Instrument List
Refresh
Updates the instrument list
– After switching on or resetting the device, wait at least one minute before
pressing the Reset button.
Apply
Stores the current instrument list in Fieldgate SWG70