36
Commissioning
7.3
Starting the generator
Power generator start-up in manual control mode (see Chapter
is de-
scribed here
.
Proceed as follows to start the power generator from the E-MCS 7.0 control mod-
ule of the operating panel.
Fig. 7-2 Manually starting and stopping the power generator
Conditions
The electrical safety has been checked (see Chapter 5 ).
The fuel tank is full enough.
The coolant level is adequate (fill with coolant before first start-up; for this,
see the engine’s operating and maintenance manual).
The oil level is adequate (fill with engine oil before initial use, see the engine
operating and maintenance manual).
There is adequate air supply and air removal.
The main battery switch must be in the “ON” position.
DANGER!
Leaking engine oil and fuel can burn or explode.
A risk of suffering severe even deadly burns.
► Prevent engine oil or fuel from leaking out.
► Never open the tank cover during operation or when it is hot.
► Remove leaked operating fluids immediately and appropriately.
► Never use an additional starting aid.
► Smoking, naked flames and sparks are forbidden.