59
The device in-use
Setting up the re-
mote start connec-
tion
Do as follows to operate the power generator from the remote starting de-
vice:
Fig. 8-8 Remote starting device with HARTING® socket
Conditions
The power generator is ready for operation.
The starter battery is properly connected.
All consumers are switched off or disconnected from the generator.
1. Firmly press the locking bracket Fig. 8-8 toward the power generator.
2. Open the HARTING® socket’s safety cap Fig. 8-8 upward.
3. Push the HARTING® plug of the external connection cable onto the HART-
ING® socket until the stop.
4. Pull the locking bracket Fig. 8-8 toward the HARTING® plug to lock it.
The remote starting device is ready to operate.
NOTICE!
Further steps for starting and stopping the power generator are in the op-
erating manual for the external component or installation.
NOTICE!
If the remote starting device is connected, the power generator CANNOT be
turned off from the control module (see Chapter 8.1 ). Use the EMERGENCY
STOP switch if an emergency occurs (see Chapter 7.6 ).
Disconnecting the
remote start con-
nection
Do as follows to disconnect the remote start connection remote control af-
ter the generator has been switched off:
1. Firmly press the locking bracket Fig. 8-8 toward the power generator.
2. Pull the HARTING® plug of the external connection cable out of the HART-
ING® socket.
3. Close the HARTING® socket’s safety cap Fig. 8-8 downward.
4. Pull the locking bracket Fig. 8-8 toward you to lock the safety cap.
The remote start connection is disconnected.